# Intake-damper open-proof gate

Canonical URL: https://eloragrid.ai/symbols/intake-damper-open-proof-gate
Publisher: Elora Grid
Updated: 2026-11-03
Lookup label: IOG
Drawing use: Schematic
Reference families: Manufacturer

Representation: Functional block
Installation focus: switchrooms
Input: Damper open proof
Output: Ventilation permission

Uses the intake-damper feedback as a condition of the assigned ventilation operation.

## In plain English

### What this block does

Uses the intake-damper feedback as a condition of the assigned ventilation operation.

### A simple example

In a switchroom containing transformers and auxiliary panels, the room controller can supervise fan availability and send an alarm when the documented ventilation duty is not achieved. For this reference, the drawing identifies “Damper open proof” at the input and “Ventilation permission” at the output. Position proof does not measure effective airflow.

### What the drawings help you do

Start at the named input: Damper open proof. Identify its source device or document and the state represented on the drawing. Follow the named output: Ventilation permission. Cross-reference its destination and separate the command from confirmation that the equipment responded.

### Terms

- Input: Damper open proof
- Output: Ventilation permission
- Application reference: An explanation of a named drawing function or circuit relationship; the project documents define the equipment and its connections.

Concept diagram: Damper open proof → IOG → Ventilation permission
A reading guide. The entry's original illustration and input/output facts describe this application.

- [Ventilation in MV substations](https://www.electrical-installation.org/enwiki/Ventilation_in_MV_Substations)


## What it represents

Uses the intake-damper feedback as a condition of the assigned ventilation operation. Ventilation control coordinates the equipment that manages heat and air movement in an electrical room. A temperature request, a fan command and proof of airflow are separate signals, and the room design determines how they interact.
In a switchroom containing transformers and auxiliary panels, the room controller can supervise fan availability and send an alarm when the documented ventilation duty is not achieved. For this reference, the drawing identifies “Damper open proof” at the input and “Ventilation permission” at the output. Position proof does not measure effective airflow.
Identify the monitored space, the selected ventilation mode and the equipment feedback. Avoid inferring airflow, temperature limits or a fire response from a generic fan symbol; these require the room-services design. The functional block is an independent explanation of this named application. Equipment-specific ratings, terminal connections and operating conditions must be established in the project documentation.

## How to read it

- Start at the named input: Damper open proof. Identify its source device or document and the state represented on the drawing.
- Follow the named output: Ventilation permission. Cross-reference its destination and separate the command from confirmation that the equipment responded.
- Position proof does not measure effective airflow.
- Identify the monitored space, the selected ventilation mode and the equipment feedback. Avoid inferring airflow, temperature limits or a fire response from a generic fan symbol; these require the room-services design.

## Information to show or reference

- Label the source and connection reference for damper open proof.
- Identify the destination and defined state of ventilation permission.
- Record the equipment or control-document revision supporting this functional block.
- Check this application limit in the project design: Position proof does not measure effective airflow.

## Important distinction

Position proof does not measure effective airflow. This reference describes the named application; it does not establish a new IEC graphical symbol, an ANSI device-function number or an exact manufacturer connection diagram.

## Facts

- Representation: Functional block
- Installation focus: Switchrooms
- Input / boundary: Damper open proof
- Output / connection: Ventilation permission
- Lookup label: IOG is a library lookup label, not a standard device designation.

## Public references

- [Ventilation in MV substations](https://www.electrical-installation.org/enwiki/Ventilation_in_MV_Substations) — Schneider Electric. Public technical context for switchroom ventilation interfaces. Heat removal, condensation and environmental design context. The application text and educational graphic are independently authored; the publisher does not certify this representation.

## Graphic scope

Independent original educational concept illustration by Elora Grid. Not a certified standards graphic or manufacturer footprint. Unitless; not to scale. Original artwork licence: https://creativecommons.org/licenses/by/4.0/. Publisher material is linked only.