{"schemaVersion":1,"slug":"irig-b-time-distribution-interface","name":"IRIG-B time-distribution interface","kind":"symbol","abbreviation":"ITI","aliases":["Substation timing and event interfaces","substations Substation timing and event interfaces","substations","Substations","IRIG-B source output","Equipment time input"],"category":"measurement-protection","drawingTypes":["Schematic"],"referenceFamilies":["Manufacturer"],"summary":"Identifies the selected coded time connection between station clock and equipment.","description":["Identifies the selected coded time connection between station clock and equipment. A station time system provides a shared time reference for protection records, measurements and automation. Different devices can use different timing protocols, so the time source, distribution path and quality information must remain identifiable.","In a substation, a station clock can provide precision timing to process equipment and another timing interface to event recorders. The alarm system should distinguish loss of a distribution path from loss of the external time source. For this reference, the drawing identifies “IRIG-B source output” at the input and “Equipment time input” at the output. Signal format and electrical interface must match.","Show the source and client of each time connection. Required accuracy, holdover, protocol profile and loss-of-time behavior follow the selected application; a common timestamp format does not guarantee synchronized events. The functional block is an independent explanation of this named application. Equipment-specific ratings, terminal connections and operating conditions must be established in the project documentation."],"readingNotes":["Start at the named input: IRIG-B source output. Identify its source device or document and the state represented on the drawing.","Follow the named output: Equipment time input. Cross-reference its destination and separate the command from confirmation that the equipment responded.","Signal format and electrical interface must match.","Show the source and client of each time connection. Required accuracy, holdover, protocol profile and loss-of-time behavior follow the selected application; a common timestamp format does not guarantee synchronized events."],"drawingChecklist":["Label the source and connection reference for irig-b source output.","Identify the destination and defined state of equipment time input.","Record the equipment or control-document revision supporting this functional block.","Check this application limit in the project design: Signal format and electrical interface must match."],"distinction":"Signal format and electrical interface must match. This reference describes the named application; it does not establish a new IEC graphical symbol, an ANSI device-function number or an exact manufacturer connection diagram.","facts":[{"label":"Representation","value":"Functional block"},{"label":"Installation focus","value":"Substations"},{"label":"Input / boundary","value":"IRIG-B source output"},{"label":"Output / connection","value":"Equipment time input"},{"label":"Lookup label","value":"ITI is a library lookup label, not a standard device designation."}],"references":[{"sourceId":"pi26-station-time","relevance":"Public technical context for substation timing and event interfaces. PTP, NTP, IRIG-B, pulse distribution, reference failover and timing quality. The application text and educational graphic are independently authored; the publisher does not certify this representation."}],"related":["sequence-of-events-recorder","phasor-measurement-unit","ntp-station-time-service-interface"],"artwork":"pi26-irig-b-time-distribution-interface","publishedOn":"2026-11-03","updatedOn":"2026-11-03","provenance":"independent-public-research","representation":{"type":"functional-block","focus":"substations","family":"station-time","input":"IRIG-B source output","output":"Equipment time input"},"plainEnglish":{"title":"What this block does","introduction":"Identifies the selected coded time connection between station clock and equipment.","example":"In a substation, a station clock can provide precision timing to process equipment and another timing interface to event recorders. The alarm system should distinguish loss of a distribution path from loss of the external time source. For this reference, the drawing identifies “IRIG-B source output” at the input and “Equipment time input” at the output. Signal format and electrical interface must match.","drawings":"Start at the named input: IRIG-B source output. Identify its source device or document and the state represented on the drawing. Follow the named output: Equipment time input. Cross-reference its destination and separate the command from confirmation that the equipment responded.","terms":[{"name":"Input","meaning":"IRIG-B source output"},{"name":"Output","meaning":"Equipment time input"},{"name":"Application reference","meaning":"An explanation of a named drawing function or circuit relationship; the project documents define the equipment and its connections."}],"diagram":"flow","steps":["IRIG-B source output","ITI","Equipment time input"],"caption":"A reading guide. The entry's original illustration and input/output facts describe this application.","sources":[{"label":"SEL-2488 satellite-synchronised network clock","url":"https://selinc.com/products/2488/"}],"profileId":"power-installation-station-time"},"url":"https://eloragrid.ai/symbols/irig-b-time-distribution-interface","illustration":{"url":"https://eloragrid.ai/tools/electrical-library/illustrations/irig-b-time-distribution-interface.svg","scope":"Original educational concept; not an official standard graphic or product footprint","license":"https://creativecommons.org/licenses/by/4.0/"},"sources":[{"id":"pi26-station-time","publisher":"SEL","title":"SEL-2488 satellite-synchronised network clock","url":"https://selinc.com/products/2488/","scope":"PTP, NTP, IRIG-B, pulse distribution, reference failover and timing quality.","type":"manufacturer","checkedOn":"2026-11-03","reuse":"link-only","relevance":"Public technical context for substation timing and event interfaces. PTP, NTP, IRIG-B, pulse distribution, reference failover and timing quality. The application text and educational graphic are independently authored; the publisher does not certify this representation."}]}