{"schemaVersion":1,"slug":"lockout-mediated-breaker-trip","name":"Lockout-mediated breaker trip","kind":"symbol","abbreviation":"LBT","aliases":["Breaker trip circuits","switchgear Breaker trip circuits","switchgear","Switchgear","Lockout initiation","Latched trip request"],"category":"control-circuits","drawingTypes":["Schematic"],"referenceFamilies":["Manufacturer"],"summary":"Passes a protection initiation through a latched lockout function before the assigned breaker trips.","description":["Passes a protection initiation through a latched lockout function before the assigned breaker trips. A trip circuit carries an opening request from a control or protection device to the breaker operating mechanism. The opening command, the coil supply and the evidence that the breaker opened are separate parts of the drawing.","In a switchgear incomer panel, a protection relay requests opening and an auxiliary contact reports the resulting breaker position. A second trip path can have its own supply and wiring so that a single wiring fault does not remove both paths. For this reference, the drawing identifies “Lockout initiation” at the input and “Latched trip request” at the output. Reset permission is separate from trip initiation.","Trace the initiating contact, protective fuse, trip coil, return conductor and feedback independently. Identify which elements are shared between redundant paths. The diagram explains the intended command path; coil ratings and terminal numbers come from the selected breaker. The functional block is an independent explanation of this named application. Equipment-specific ratings, terminal connections and operating conditions must be established in the project documentation."],"readingNotes":["Start at the named input: Lockout initiation. Identify its source device or document and the state represented on the drawing.","Follow the named output: Latched trip request. Cross-reference its destination and separate the command from confirmation that the equipment responded.","Reset permission is separate from trip initiation.","Trace the initiating contact, protective fuse, trip coil, return conductor and feedback independently. Identify which elements are shared between redundant paths. The diagram explains the intended command path; coil ratings and terminal numbers come from the selected breaker."],"drawingChecklist":["Label the source and connection reference for lockout initiation.","Identify the destination and defined state of latched trip request.","Record the equipment or control-document revision supporting this functional block.","Check this application limit in the project design: Reset permission is separate from trip initiation."],"distinction":"Reset permission is separate from trip initiation. This reference describes the named application; it does not establish a new IEC graphical symbol, an ANSI device-function number or an exact manufacturer connection diagram.","facts":[{"label":"Representation","value":"Functional block"},{"label":"Installation focus","value":"Switchgear"},{"label":"Input / boundary","value":"Lockout initiation"},{"label":"Output / connection","value":"Latched trip request"},{"label":"Lookup label","value":"LBT is a library lookup label, not a standard device designation."}],"references":[{"sourceId":"pi26-masterclad","relevance":"Public technical context for breaker trip circuits. Breaker control, mechanism, position contacts, racking interlocks and test interfaces. The application text and educational graphic are independently authored; the publisher does not certify this representation."}],"related":["circuit-breaker","86-lockout","direct-protection-to-coil-trip"],"artwork":"pi26-lockout-mediated-breaker-trip","publishedOn":"2026-11-03","updatedOn":"2026-11-03","provenance":"independent-public-research","representation":{"type":"functional-block","focus":"switchgear","family":"trip","input":"Lockout initiation","output":"Latched trip request"},"plainEnglish":{"title":"What this block does","introduction":"Passes a protection initiation through a latched lockout function before the assigned breaker trips.","example":"In a switchgear incomer panel, a protection relay requests opening and an auxiliary contact reports the resulting breaker position. A second trip path can have its own supply and wiring so that a single wiring fault does not remove both paths. For this reference, the drawing identifies “Lockout initiation” at the input and “Latched trip request” at the output. Reset permission is separate from trip initiation.","drawings":"Start at the named input: Lockout initiation. Identify its source device or document and the state represented on the drawing. Follow the named output: Latched trip request. Cross-reference its destination and separate the command from confirmation that the equipment responded.","terms":[{"name":"Input","meaning":"Lockout initiation"},{"name":"Output","meaning":"Latched trip request"},{"name":"Application reference","meaning":"An explanation of a named drawing function or circuit relationship; the project documents define the equipment and its connections."}],"diagram":"flow","steps":["Lockout initiation","LBT","Latched trip request"],"caption":"A reading guide. The entry's original illustration and input/output facts describe this application.","sources":[{"label":"Masterclad medium-voltage switchgear: circuit-breaker section interlocks","url":"https://productinfo.se.com/masterclad_mv_switchgear_ib/6055-30-masterclad-15kv-mv-switchgear-ib/English/6055-30%20Masterclad%20MV%20Switchgear%20Indoor%20%28bookmap%29_DD00646805.xml/%24/Section6-CircuitBreakerSectionInter-58DD6EC7"}],"profileId":"power-installation-trip"},"url":"https://eloragrid.ai/symbols/lockout-mediated-breaker-trip","illustration":{"url":"https://eloragrid.ai/tools/electrical-library/illustrations/lockout-mediated-breaker-trip.svg","scope":"Original educational concept; not an official standard graphic or product footprint","license":"https://creativecommons.org/licenses/by/4.0/"},"sources":[{"id":"pi26-masterclad","publisher":"Schneider Electric","title":"Masterclad medium-voltage switchgear: circuit-breaker section interlocks","url":"https://productinfo.se.com/masterclad_mv_switchgear_ib/6055-30-masterclad-15kv-mv-switchgear-ib/English/6055-30%20Masterclad%20MV%20Switchgear%20Indoor%20%28bookmap%29_DD00646805.xml/%24/Section6-CircuitBreakerSectionInter-58DD6EC7","scope":"Breaker control, mechanism, position contacts, racking interlocks and test interfaces.","type":"manufacturer","checkedOn":"2026-11-03","reuse":"link-only","relevance":"Public technical context for breaker trip circuits. Breaker control, mechanism, position contacts, racking interlocks and test interfaces. The application text and educational graphic are independently authored; the publisher does not certify this representation."}]}