{"schemaVersion":1,"slug":"microgrid-close-command-confirmation-interface","name":"Microgrid close-command confirmation interface","kind":"symbol","abbreviation":"MCCI","aliases":["Microgrid synchronising interfaces","microgrids Microgrid synchronising interfaces","microgrids","Microgrids","PCC close request and position","Reconnection completion status"],"category":"microgrid-systems","drawingTypes":["Schematic"],"referenceFamilies":["Manufacturer"],"summary":"Compares the issued PCC closing request with its assigned breaker feedback.","description":["Compares the issued PCC closing request with its assigned breaker feedback. Synchronising control compares two AC systems before their assigned connecting breaker closes. Voltage magnitude, frequency, phase relationship, breaker readiness and command authority are separate inputs to the closing decision.","In a microgrid reconnecting at its point of common coupling, a synchroniser can adjust the island reference while a separate permissive confirms the permitted relationship across the open breaker. For this reference, the drawing identifies “PCC close request and position” at the input and “Reconnection completion status” at the output. A sent command does not prove a closed breaker.","Identify the two measurement sides and the equipment receiving any adjustment request. Closing limits, breaker timing and loss-of-measurement behavior require the approved synchronising design. The functional block is an independent explanation of this named application. Equipment-specific ratings, terminal connections and operating conditions must be established in the project documentation."],"readingNotes":["Start at the named input: PCC close request and position. Identify its source device or document and the state represented on the drawing.","Follow the named output: Reconnection completion status. Cross-reference its destination and separate the command from confirmation that the equipment responded.","A sent command does not prove a closed breaker.","Identify the two measurement sides and the equipment receiving any adjustment request. Closing limits, breaker timing and loss-of-measurement behavior require the approved synchronising design."],"drawingChecklist":["Label the source and connection reference for pcc close request and position.","Identify the destination and defined state of reconnection completion status.","Record the equipment or control-document revision supporting this functional block.","Check this application limit in the project design: A sent command does not prove a closed breaker."],"distinction":"A sent command does not prove a closed breaker. This reference describes the named application; it does not establish a new IEC graphical symbol, an ANSI device-function number or an exact manufacturer connection diagram.","facts":[{"label":"Representation","value":"Functional block"},{"label":"Installation focus","value":"Microgrids"},{"label":"Input / boundary","value":"PCC close request and position"},{"label":"Output / connection","value":"Reconnection completion status"},{"label":"Lookup label","value":"MCCI is a library lookup label, not a standard device designation."}],"references":[{"sourceId":"pi26-mg-design","relevance":"Public technical context for microgrid synchronising interfaces. Microgrid power and control interfaces, synchronisation and source coordination. The application text and educational graphic are independently authored; the publisher does not certify this representation."}],"related":["25-synchronism-check","synchronoscope","microgrid-failed-reconnect-restraint"],"artwork":"pi26-microgrid-close-command-confirmation-interface","publishedOn":"2026-11-03","updatedOn":"2026-11-03","provenance":"independent-public-research","representation":{"type":"functional-block","focus":"microgrids","family":"microgrid-sync","input":"PCC close request and position","output":"Reconnection completion status"},"plainEnglish":{"title":"What this block does","introduction":"Compares the issued PCC closing request with its assigned breaker feedback.","example":"In a microgrid reconnecting at its point of common coupling, a synchroniser can adjust the island reference while a separate permissive confirms the permitted relationship across the open breaker. For this reference, the drawing identifies “PCC close request and position” at the input and “Reconnection completion status” at the output. A sent command does not prove a closed breaker.","drawings":"Start at the named input: PCC close request and position. Identify its source device or document and the state represented on the drawing. Follow the named output: Reconnection completion status. Cross-reference its destination and separate the command from confirmation that the equipment responded.","terms":[{"name":"Input","meaning":"PCC close request and position"},{"name":"Output","meaning":"Reconnection completion status"},{"name":"Application reference","meaning":"An explanation of a named drawing function or circuit relationship; the project documents define the equipment and its connections."}],"diagram":"flow","steps":["PCC close request and position","MCCI","Reconnection completion status"],"caption":"A reading guide. The entry's original illustration and input/output facts describe this application.","sources":[{"label":"Microgrid Flex components and control design","url":"https://productinfo.se.com/microgrid_guide/0100db2503_ecostruxure-microgrid-flex_design-guide_iec/English/0100DB2503-Microgrid%20Flex%20Design%20Guide-IEC-Optimize%20%28bookmap%29_DD00654397.XML.xml/%24/MicrogridFlexComponents-3A7DD96C"}],"profileId":"power-installation-microgrid-sync"},"url":"https://eloragrid.ai/symbols/microgrid-close-command-confirmation-interface","illustration":{"url":"https://eloragrid.ai/tools/electrical-library/illustrations/microgrid-close-command-confirmation-interface.svg","scope":"Original educational concept; not an official standard graphic or product footprint","license":"https://creativecommons.org/licenses/by/4.0/"},"sources":[{"id":"pi26-mg-design","publisher":"Schneider Electric","title":"Microgrid Flex components and control design","url":"https://productinfo.se.com/microgrid_guide/0100db2503_ecostruxure-microgrid-flex_design-guide_iec/English/0100DB2503-Microgrid%20Flex%20Design%20Guide-IEC-Optimize%20%28bookmap%29_DD00654397.XML.xml/%24/MicrogridFlexComponents-3A7DD96C","scope":"Microgrid power and control interfaces, synchronisation and source coordination.","type":"manufacturer","checkedOn":"2026-11-03","reuse":"link-only","relevance":"Public technical context for microgrid synchronising interfaces. Microgrid power and control interfaces, synchronisation and source coordination. The application text and educational graphic are independently authored; the publisher does not certify this representation."}]}