{"schemaVersion":1,"slug":"microgrid-dead-utility-island-close-restraint","name":"Microgrid dead-utility island-close restraint","kind":"symbol","abbreviation":"MDIR","aliases":["Microgrid synchronising interfaces","microgrids Microgrid synchronising interfaces","microgrids","Microgrids","Island voltage and utility condition","Interconnection closing restraint"],"category":"microgrid-systems","drawingTypes":["Schematic"],"referenceFamilies":["Manufacturer"],"summary":"Identifies the specified restraint on connecting an energized island to an unavailable utility circuit.","description":["Identifies the specified restraint on connecting an energized island to an unavailable utility circuit. Synchronising control compares two AC systems before their assigned connecting breaker closes. Voltage magnitude, frequency, phase relationship, breaker readiness and command authority are separate inputs to the closing decision.","In a microgrid reconnecting at its point of common coupling, a synchroniser can adjust the island reference while a separate permissive confirms the permitted relationship across the open breaker. For this reference, the drawing identifies “Island voltage and utility condition” at the input and “Interconnection closing restraint” at the output. Connection permission follows the network agreement.","Identify the two measurement sides and the equipment receiving any adjustment request. Closing limits, breaker timing and loss-of-measurement behavior require the approved synchronising design. The functional block is an independent explanation of this named application. Equipment-specific ratings, terminal connections and operating conditions must be established in the project documentation."],"readingNotes":["Start at the named input: Island voltage and utility condition. Identify its source device or document and the state represented on the drawing.","Follow the named output: Interconnection closing restraint. Cross-reference its destination and separate the command from confirmation that the equipment responded.","Connection permission follows the network agreement.","Identify the two measurement sides and the equipment receiving any adjustment request. Closing limits, breaker timing and loss-of-measurement behavior require the approved synchronising design."],"drawingChecklist":["Label the source and connection reference for island voltage and utility condition.","Identify the destination and defined state of interconnection closing restraint.","Record the equipment or control-document revision supporting this functional block.","Check this application limit in the project design: Connection permission follows the network agreement."],"distinction":"Connection permission follows the network agreement. This reference describes the named application; it does not establish a new IEC graphical symbol, an ANSI device-function number or an exact manufacturer connection diagram.","facts":[{"label":"Representation","value":"Functional block"},{"label":"Installation focus","value":"Microgrids"},{"label":"Input / boundary","value":"Island voltage and utility condition"},{"label":"Output / connection","value":"Interconnection closing restraint"},{"label":"Lookup label","value":"MDIR is a library lookup label, not a standard device designation."}],"references":[{"sourceId":"pi26-mg-design","relevance":"Public technical context for microgrid synchronising interfaces. Microgrid power and control interfaces, synchronisation and source coordination. The application text and educational graphic are independently authored; the publisher does not certify this representation."}],"related":["25-synchronism-check","synchronoscope","microgrid-synchronising-measurement-quality-gate"],"artwork":"pi26-microgrid-dead-utility-island-close-restraint","publishedOn":"2026-11-03","updatedOn":"2026-11-03","provenance":"independent-public-research","representation":{"type":"functional-block","focus":"microgrids","family":"microgrid-sync","input":"Island voltage and utility condition","output":"Interconnection closing restraint"},"plainEnglish":{"title":"What this block does","introduction":"Identifies the specified restraint on connecting an energized island to an unavailable utility circuit.","example":"In a microgrid reconnecting at its point of common coupling, a synchroniser can adjust the island reference while a separate permissive confirms the permitted relationship across the open breaker. For this reference, the drawing identifies “Island voltage and utility condition” at the input and “Interconnection closing restraint” at the output. Connection permission follows the network agreement.","drawings":"Start at the named input: Island voltage and utility condition. Identify its source device or document and the state represented on the drawing. Follow the named output: Interconnection closing restraint. Cross-reference its destination and separate the command from confirmation that the equipment responded.","terms":[{"name":"Input","meaning":"Island voltage and utility condition"},{"name":"Output","meaning":"Interconnection closing restraint"},{"name":"Application reference","meaning":"An explanation of a named drawing function or circuit relationship; the project documents define the equipment and its connections."}],"diagram":"flow","steps":["Island voltage and utility condition","MDIR","Interconnection closing restraint"],"caption":"A reading guide. The entry's original illustration and input/output facts describe this application.","sources":[{"label":"Microgrid Flex components and control design","url":"https://productinfo.se.com/microgrid_guide/0100db2503_ecostruxure-microgrid-flex_design-guide_iec/English/0100DB2503-Microgrid%20Flex%20Design%20Guide-IEC-Optimize%20%28bookmap%29_DD00654397.XML.xml/%24/MicrogridFlexComponents-3A7DD96C"}],"profileId":"power-installation-microgrid-sync"},"url":"https://eloragrid.ai/symbols/microgrid-dead-utility-island-close-restraint","illustration":{"url":"https://eloragrid.ai/tools/electrical-library/illustrations/microgrid-dead-utility-island-close-restraint.svg","scope":"Original educational concept; not an official standard graphic or product footprint","license":"https://creativecommons.org/licenses/by/4.0/"},"sources":[{"id":"pi26-mg-design","publisher":"Schneider Electric","title":"Microgrid Flex components and control design","url":"https://productinfo.se.com/microgrid_guide/0100db2503_ecostruxure-microgrid-flex_design-guide_iec/English/0100DB2503-Microgrid%20Flex%20Design%20Guide-IEC-Optimize%20%28bookmap%29_DD00654397.XML.xml/%24/MicrogridFlexComponents-3A7DD96C","scope":"Microgrid power and control interfaces, synchronisation and source coordination.","type":"manufacturer","checkedOn":"2026-11-03","reuse":"link-only","relevance":"Public technical context for microgrid synchronising interfaces. Microgrid power and control interfaces, synchronisation and source coordination. The application text and educational graphic are independently authored; the publisher does not certify this representation."}]}