{"schemaVersion":1,"slug":"static-var-compensator","name":"Static var compensator","kind":"symbol","abbreviation":"SVC","aliases":["SVC","static VAr compensator","thyristor-based reactive compensator"],"category":"microgrid-systems","drawingTypes":["SLD"],"referenceFamilies":["IEC","IEEE / ANSI"],"summary":"A shunt reactive power compensator built from thyristor-controlled reactors, thyristor-switched capacitors and filters.","description":["A static var compensator is a shunt-connected installation that controls voltage by rapidly varying the reactive power it exchanges with the network. Its branches are typically a thyristor-controlled reactor, one or more thyristor-switched capacitors and harmonic filters, all connected to the secondary of a dedicated step-down transformer.","Single-line diagrams show the compensator transformer feeding a medium-voltage bus with each branch drawn separately, or a summary block labelled SVC with a variable capacitor-reactor symbol. It is used at transmission substations, at large industrial loads such as arc furnaces and at some renewable connection points.","Because its output is based on switched reactances, available reactive current falls with voltage, so it gives less support during deep voltage dips than a STATCOM. The symbol does not show the control slope, the branch ratings or the harmonic performance."],"readingNotes":["Read each branch rating to find the inductive and capacitive range.","Filters in an SVC usually also supply part of the capacitive output."],"drawingChecklist":["State capacitive and inductive range in Mvar.","Show transformer and branches.","Reference voltage control slope."],"distinction":"An SVC varies switched reactances; a STATCOM uses a voltage-source converter and holds output current better at low voltage.","facts":[{"label":"Branches","value":"TCR, TSC and harmonic filters"},{"label":"Connection","value":"Shunt, usually through a transformer"},{"label":"Low-voltage behaviour","value":"Output falls with voltage squared"},{"label":"Preview","value":"Independent educational illustration; consult the applicable standard and project legend for the exact graphic"}],"references":[{"sourceId":"s28-hitachi-svc","relevance":"Public SVC page describing TCR, TSC and harmonic filter branches."},{"sourceId":"iec-diagrams","relevance":"IEC graphical symbol context for reactors and capacitors."}],"related":["thyristor-controlled-reactor","thyristor-switched-capacitor","statcom","single-tuned-harmonic-filter"],"artwork":"s28-static-var-compensator","publishedOn":"2026-10-28","updatedOn":"2026-10-28","provenance":"independent-public-research","plainEnglish":{"title":"What does Static var compensator mean?","introduction":"A static var compensator is a shunt-connected installation that controls voltage by rapidly varying the reactive power it exchanges with the network. Its branches are typically a thyristor-controlled reactor, one or more thyristor-switched capacitors and harmonic filters, all connected to the secondary of a dedicated step-down transformer.","example":"Single-line diagrams show the compensator transformer feeding a medium-voltage bus with each branch drawn separately, or a summary block labelled SVC with a variable capacitor-reactor symbol. It is used at transmission substations, at large industrial loads such as arc furnaces and at some renewable connection points.","drawings":"Because its output is based on switched reactances, available reactive current falls with voltage, so it gives less support during deep voltage dips than a STATCOM. The symbol does not show the control slope, the branch ratings or the harmonic performance.","terms":[{"name":"Winding","meaning":"A coil of conductor inside an electrical machine or transformer."},{"name":"Terminal","meaning":"An identified point where a conductor connects."},{"name":"Signal","meaning":"Electrical information passed between devices, rather than necessarily the main power supply."}],"diagram":"flow","steps":["Identify the device and form","Read the connections and state","Check the equipment reference"],"caption":"A guide to reading this reference. The original symbol illustration and its drawing notes appear below; these boxes are not a wiring diagram.","sources":[{"label":"Static Var Compensators (SVC)","url":"https://www.hitachienergy.com/products-and-solutions/facts/static-var-compensation-svc"},{"label":"IEC graphical symbols for diagrams","url":"https://tc3.iec.ch/tc-activity/graphical-symbols-for-diagrams/"}],"detail":"A shunt reactive power compensator built from thyristor-controlled reactors, thyristor-switched capacitors and filters. An SVC varies switched reactances; a STATCOM uses a voltage-source converter and holds output current better at low voltage.","profileId":"reviewed-symbol-20261028"},"url":"https://eloragrid.ai/symbols/static-var-compensator","illustration":{"url":"https://eloragrid.ai/tools/electrical-library/illustrations/static-var-compensator.svg","scope":"Original educational concept; not an official standard graphic or product footprint","license":"https://creativecommons.org/licenses/by/4.0/"},"sources":[{"id":"s28-hitachi-svc","title":"Static Var Compensators (SVC)","publisher":"Hitachi Energy","url":"https://www.hitachienergy.com/products-and-solutions/facts/static-var-compensation-svc","type":"manufacturer","scope":"Public SVC description naming thyristor-controlled reactor, thyristor-switched capacitor and harmonic filter branches.","checkedOn":"2026-10-28","reuse":"link-only","relevance":"Public SVC page describing TCR, TSC and harmonic filter branches."},{"id":"iec-diagrams","title":"IEC graphical symbols for diagrams","publisher":"IEC","url":"https://tc3.iec.ch/tc-activity/graphical-symbols-for-diagrams/","type":"standard","scope":"IEC 60617 and related symbol-design publications. Full database access requires a subscription.","checkedOn":"2026-10-13","reuse":"link-only","relevance":"IEC graphical symbol context for reactors and capacitors."}]}