# Wound-primary current transformer

Canonical URL: https://eloragrid.ai/symbols/wound-primary-current-transformer
Publisher: Elora Grid
Updated: 2026-10-28
Lookup label: CT
Drawing use: SLD, Schematic
Reference families: IEC, Manufacturer

CT with a primary winding of several turns, used for low primary currents where a bar primary gives too little accuracy.

## In plain English

### What does Wound-primary current transformer mean?

A wound-primary CT has a primary winding of more than one turn rather than a single bar or conductor through a window. This is needed at low primary currents, where a single turn would not produce enough magnetising ampere-turns for accurate metering, and it is common in MV metering units.

### A simple example

The wound primary has a lower short-time withstand than a bar primary, so its thermal and dynamic ratings need checking against the fault level. The symbol shows the winding but not those ratings, which belong in the CT schedule.

### What the drawings help you do

Check the short-time thermal rating against the fault level. Read primary terminals P1 and P2 for polarity. A wound-primary CT has a multi-turn primary; a window or bar CT uses the circuit conductor as a single-turn primary.

### This particular reference

CT with a primary winding of several turns, used for low primary currents where a bar primary gives too little accuracy. A wound-primary CT has a multi-turn primary; a window or bar CT uses the circuit conductor as a single-turn primary.

### Terms

- Winding: A coil of conductor inside an electrical machine or transformer.
- Rating: A value stating the conditions for which equipment is specified.
- Schematic: A drawing showing function and connections rather than physical appearance.

Concept diagram: Identify the device and form → Read the connections and state → Check the equipment reference
A guide to reading this reference. The original symbol illustration and its drawing notes appear below; these boxes are not a wiring diagram.

- [Indoor current and voltage transformers](https://www.abb.com/gb/en/areas/electrification/medium-voltage/grid-components/core-components/indoor-instrument-transformers)
- [Current transformer symbol variants](https://help.autodesk.com/cloudhelp/2021/ENU/AutoCAD-Electrical/files/GUID-40AAEF4A-AC3F-4B3D-90A5-A9E0707C1241.htm)


## What it represents

A wound-primary CT has a primary winding of more than one turn rather than a single bar or conductor through a window. This is needed at low primary currents, where a single turn would not produce enough magnetising ampere-turns for accurate metering, and it is common in MV metering units.
The wound primary has a lower short-time withstand than a bar primary, so its thermal and dynamic ratings need checking against the fault level. The symbol shows the winding but not those ratings, which belong in the CT schedule.

## How to read it

- Check the short-time thermal rating against the fault level.
- Read primary terminals P1 and P2 for polarity.

## Information to show or reference

- State ratio and class
- Give short-time rating
- Show polarity marks

## Important distinction

A wound-primary CT has a multi-turn primary; a window or bar CT uses the circuit conductor as a single-turn primary.

## Facts

- Primary: Multi-turn winding
- Typical use: Low primary currents and metering units
- Preview: Independent educational concept; consult the applicable standard and project legend for the exact graphic

## Public references

- [Indoor current and voltage transformers](https://www.abb.com/gb/en/areas/electrification/medium-voltage/grid-components/core-components/indoor-instrument-transformers) — ABB. Public manufacturer overview of indoor current and voltage instrument transformers.
- [Current transformer symbol variants](https://help.autodesk.com/cloudhelp/2021/ENU/AutoCAD-Electrical/files/GUID-40AAEF4A-AC3F-4B3D-90A5-A9E0707C1241.htm) — Autodesk. Public AutoCAD Electrical current transformer family used for context; this variant is independently drawn.

## Graphic scope

Independent original educational concept illustration by Elora Grid. Not a certified standards graphic or manufacturer footprint. Unitless; not to scale. Original artwork licence: https://creativecommons.org/licenses/by/4.0/. Publisher material is linked only.