Earth-fault current relay
Measuring relay form that operates on current flowing to earth, fed from a residual connection or core-balance CT.
IEEE-library form of earth-fault current relay: measuring relay form that operates on current flowing to earth, fed from a residual connection or core-balance CT.
In plain English
This reference locates earth-fault current relay in Autodesk's IEEE-oriented current protection relays family. The earth-fault current relay form identifies a relay whose operating quantity is current flowing to earth. It may be fed from a core-balance CT around all live conductors, from the residual connection of three phase CTs, or from a CT in the star-point earth lead, and the source changes its achievable sensitivity. The public library uses HCR1F37 for its horizontal representation; this is a vendor block name, not an IEEE standards symbol number.
Trace the measured quantity or initiating control signal separately from the output contacts. The device tag links the sensing or operating element to the controlled circuit; settings, reset behaviour and the actual terminal arrangement belong in the selected equipment documentation.
The relay box shows the quantity with an earth additional drawing mark but not the setting, characteristic or whether it is directional. In resistance-earthed and isolated networks earth-fault current is small and often needs a sensitive or directional element that must be stated separately. Identify the CT arrangement that supplies the residual current. An earth-fault current relay measures current to earth; an earth-fault voltage relay measures neutral displacement voltage. The linked functional counterpart explains the same operating role in its own drawing context; agreement of every detailed convention mark is not asserted.
IEEE-library form of earth-fault current relay: measuring relay form that operates on current flowing to earth, fed from a residual connection or core-balance CT. An earth-fault current relay measures current to earth; an earth-fault voltage relay measures neutral displacement voltage.
Read the source: Autodesk IEEE Symbol Preview: Current Protection Relays
Autodesk IEEE Symbol Preview: Current Protection Relays, block HCR1F37. Matching functional counterpart linked separately. Independently drawn educational geometry; not a certified IEEE glyph or database identifier.
Shown as an independently authored educational illustration. Use the cited publication and drawing legend to verify the required drafting form.
This reference locates earth-fault current relay in Autodesk's IEEE-oriented current protection relays family. The earth-fault current relay form identifies a relay whose operating quantity is current flowing to earth. It may be fed from a core-balance CT around all live conductors, from the residual connection of three phase CTs, or from a CT in the star-point earth lead, and the source changes its achievable sensitivity. The public library uses HCR1F37 for its horizontal representation; this is a vendor block name, not an IEEE standards symbol number.
Trace the measured quantity or initiating control signal separately from the output contacts. The device tag links the sensing or operating element to the controlled circuit; settings, reset behaviour and the actual terminal arrangement belong in the selected equipment documentation.
The relay box shows the quantity with an earth qualifier but not the setting, characteristic or whether it is directional. In resistance-earthed and isolated networks earth-fault current is small and often needs a sensitive or directional element that must be stated separately. Identify the CT arrangement that supplies the residual current. An earth-fault current relay measures current to earth; an earth-fault voltage relay measures neutral displacement voltage. The linked functional counterpart explains the same operating role in its own drawing context; agreement of every detailed convention mark is not asserted.
An earth-fault current relay measures current to earth; an earth-fault voltage relay measures neutral displacement voltage.
These public references support the explanation and provide further detail. Their graphics and downloadable files remain with their publishers.
Public IEEE-oriented Current Protection Relays table explicitly lists HCR1F37 as Ground Failure Current Protection. This supports the vendor convention context, not reproduction of the publisher graphic.