IEEE / ANSI · IMD

ANSI/IEEE Insulation monitoring relay form

IEEE-library form of insulation monitoring relay: relay that continuously checks insulation resistance of an unearthed (IT) system to earth and alarms on a first fault.

In plain English

What does ANSI/IEEE Insulation monitoring relay form mean?

This reference locates insulation monitoring relay in Autodesk's IEEE-oriented miscellaneous relays family. An insulation monitoring relay is connected between the conductors of an unearthed (IT) system and earth, and injects a measuring signal to determine insulation resistance. It warns when insulation falls below its setting so a first fault can be located before a second fault causes a trip. The public library uses HCR1F44 for its horizontal representation; this is a vendor block name, not an IEEE standards symbol number.

A simple example

Trace the measured quantity or initiating control signal separately from the output contacts. The device tag links the sensing or operating element to the controlled circuit; settings, reset behaviour and the actual terminal arrangement belong in the selected equipment documentation.

Identify the device and formRead the connections and stateCheck the equipment reference
A guide to reading this reference. The original symbol illustration and its drawing notes appear below; these boxes are not a wiring diagram.

What the drawings help you do

The symbol shows the device and its connections but not the measuring method, which matters on systems with drives or large DC components. Only one insulation monitor should normally be active on a galvanically connected system, so the drawing should show any disconnection or interlock between parallel systems. Check that only one monitor is active on each connected IT system. An insulation monitoring relay measures insulation resistance of an unearthed system; a residual current monitor measures leakage current in an earthed system. The linked functional counterpart explains the same operating role in its own drawing context; agreement of every detailed convention mark is not asserted.

This particular reference

IEEE-library form of insulation monitoring relay: relay that continuously checks insulation resistance of an unearthed (IT) system to earth and alarms on a first fault. An insulation monitoring relay measures insulation resistance of an unearthed system; a residual current monitor measures leakage current in an earthed system.

DC
Direct current: electricity flowing in one direction.
Normally open / normally closed
The contact state in the normal condition defined for the drawing.
Coil
A wound conductor that can produce a magnetic field when energised.

Read the source: Autodesk IEEE Symbol Preview: Miscellaneous Relays · IEC graphical symbols for diagrams

IEEE / ANSI · Insulating Relay

Autodesk IEEE Symbol Preview: Miscellaneous Relays, block HCR1F44. Matching functional counterpart linked separately. Independently drawn educational geometry; not a certified IEEE glyph or database identifier.

Shown as an independently authored educational illustration. Use the cited publication and drawing legend to verify the required drafting form.

Schematic / SLD · IMDANSI/IEEE Insulation monitoring relay form: original educational illustration
Original educational illustrationNot to scale · See source and graphic notes

What it represents

This reference locates insulation monitoring relay in Autodesk's IEEE-oriented miscellaneous relays family. An insulation monitoring relay is connected between the conductors of an unearthed (IT) system and earth, and injects a measuring signal to determine insulation resistance. It warns when insulation falls below its setting so a first fault can be located before a second fault causes a trip. The public library uses HCR1F44 for its horizontal representation; this is a vendor block name, not an IEEE standards symbol number.

Trace the measured quantity or initiating control signal separately from the output contacts. The device tag links the sensing or operating element to the controlled circuit; settings, reset behaviour and the actual terminal arrangement belong in the selected equipment documentation.

The symbol shows the device and its connections but not the measuring method, which matters on systems with drives or large DC components. Only one insulation monitor should normally be active on a galvanically connected system, so the drawing should show any disconnection or interlock between parallel systems. Check that only one monitor is active on each connected IT system. An insulation monitoring relay measures insulation resistance of an unearthed system; a residual current monitor measures leakage current in an earthed system. The linked functional counterpart explains the same operating role in its own drawing context; agreement of every detailed convention mark is not asserted.

How to read it

  • Check that only one monitor is active on each connected IT system.
  • Identify alarm outputs and test button wiring.

Information to show or reference

  • Show system and earth connections
  • State alarm thresholds
  • Reference interlock between parallel monitors

A distinction that matters

An insulation monitoring relay measures insulation resistance of an unearthed system; a residual current monitor measures leakage current in an earthed system.

Sources you can follow

These public references support the explanation and provide further detail. Their graphics and downloadable files remain with their publishers.

Autodesk IEEE Symbol Preview: Miscellaneous Relays

Public IEEE-oriented Miscellaneous Relays table explicitly lists HCR1F44 as Insulating Relay. This supports the vendor convention context, not reproduction of the publisher graphic.

Autodesk · Public reference checked 28 October 2026 · Link only

IEC graphical symbols for diagrams

IEC context for graphical symbols used in diagrams; no IEC graphic is reproduced.

IEC · Public reference checked 13 October 2026 · Link only

About this graphic

This illustration was authored independently by Elora Grid to explain the concept. It is not reproduced from a customer drawing, an official standard graphic or a manufacturer CAD file. Its correspondence to an exact IEC or IEEE symbol identifier has not been certified.

SVG and DXF downloads contain this original artwork. DXF uses unscaled drawing units; a GA envelope supplies no product dimensions, clearances or fabrication information. Original artwork is available under CC BY 4.0. Third-party references retain their own terms.

Entry JSON · Entry Markdown · Last editorial update: 28 October 2026

Put the reference into a drawing workflow.

Elora Grid helps electrical teams work with drawings, specifications and equipment information. Explore the drafting workflow or join the early-access waitlist.

Explore drafting