Minimum-impedance measuring relay
Measuring relay that compares voltage with current and operates when the apparent impedance falls below a set value.
IEEE-library form of minimum-impedance measuring relay: measuring relay that compares voltage with current and operates when the apparent impedance falls below a set value.
In plain English
This reference locates minimum-impedance measuring relay in Autodesk's IEEE-oriented miscellaneous relays family. A minimum-impedance relay divides measured voltage by measured current and operates when the result falls below its setting, indicating a fault close enough to fall inside its reach. It is used as generator and transformer backup protection and is the basic idea behind distance protection. The public library uses HCR1F41 for its horizontal representation; this is a vendor block name, not an IEEE standards symbol number.
Trace the measured quantity or initiating control signal separately from the output contacts. The device tag links the sensing or operating element to the controlled circuit; settings, reset behaviour and the actual terminal arrangement belong in the selected equipment documentation.
The relay needs both CT and VT inputs, so the symbol should always be read with both connections. It does not show the characteristic shape on the impedance plane, any directional element, or the loss-of-voltage blocking needed to avoid operation when the VT supply fails. Confirm both voltage and current inputs are shown. A minimum-impedance relay uses voltage and current together; an overcurrent relay uses current alone. The linked functional counterpart explains the same operating role in its own drawing context; agreement of every detailed convention mark is not asserted.
IEEE-library form of minimum-impedance measuring relay: measuring relay that compares voltage with current and operates when the apparent impedance falls below a set value. A minimum-impedance relay uses voltage and current together; an overcurrent relay uses current alone.
Read the source: Autodesk IEEE Symbol Preview: Miscellaneous Relays · IEC graphical symbols for diagrams
Autodesk IEEE Symbol Preview: Miscellaneous Relays, block HCR1F41. Matching functional counterpart linked separately. Independently drawn educational geometry; not a certified IEEE glyph or database identifier.
Shown as an independently authored educational illustration. Use the cited publication and drawing legend to verify the required drafting form.
This reference locates minimum-impedance measuring relay in Autodesk's IEEE-oriented miscellaneous relays family. A minimum-impedance relay divides measured voltage by measured current and operates when the result falls below its setting, indicating a fault close enough to fall inside its reach. It is used as generator and transformer backup protection and is the basic idea behind distance protection. The public library uses HCR1F41 for its horizontal representation; this is a vendor block name, not an IEEE standards symbol number.
Trace the measured quantity or initiating control signal separately from the output contacts. The device tag links the sensing or operating element to the controlled circuit; settings, reset behaviour and the actual terminal arrangement belong in the selected equipment documentation.
The relay needs both CT and VT inputs, so the symbol should always be read with both connections. It does not show the characteristic shape on the impedance plane, any directional element, or the loss-of-voltage blocking needed to avoid operation when the VT supply fails. Confirm both voltage and current inputs are shown. A minimum-impedance relay uses voltage and current together; an overcurrent relay uses current alone. The linked functional counterpart explains the same operating role in its own drawing context; agreement of every detailed convention mark is not asserted.
A minimum-impedance relay uses voltage and current together; an overcurrent relay uses current alone.
These public references support the explanation and provide further detail. Their graphics and downloadable files remain with their publishers.
Public IEEE-oriented Miscellaneous Relays table explicitly lists HCR1F41 as Minimum Impedance Relay. This supports the vendor convention context, not reproduction of the publisher graphic.
IEC context for graphical symbols used in diagrams; no IEC graphic is reproduced.
This illustration was authored independently by Elora Grid to explain the concept. It is not reproduced from a customer drawing, an official standard graphic or a manufacturer CAD file. Its correspondence to an exact IEC or IEEE symbol identifier has not been certified.
SVG and DXF downloads contain this original artwork. DXF uses unscaled drawing units; a GA envelope supplies no product dimensions, clearances or fabrication information. Original artwork is available under CC BY 4.0. Third-party references retain their own terms.
Elora Grid helps electrical teams work with drawings, specifications and equipment information. Explore the drafting workflow or join the early-access waitlist.