Power transformer
Equipment transferring electrical power between winding circuits.
Gas-and-oil actuated relay in the pipe to the conservator, giving alarm on gas build-up and trip on oil surge.
In plain English
A Buchholz relay is fitted in the pipe between an oil-filled transformer tank and its conservator. Slow gas accumulation from minor internal faults operates an alarm float, while a rapid surge of oil from a serious internal fault operates a trip element, so the schematic shows two separate contacts.
On single-line diagrams it may appear only as a label on the transformer, while the control schematic shows its alarm and trip contacts wired to alarm indication and the transformer trip relay. The symbol does not show the gas sampling procedure or the test arrangement used during maintenance.
Identify separate alarm and trip contacts. Follow the trip contact to the transformer lockout or trip relay. A Buchholz relay detects gas and oil movement; a sudden pressure relay responds to rapid tank pressure rise.
Gas-and-oil actuated relay in the pipe to the conservator, giving alarm on gas build-up and trip on oil surge. A Buchholz relay detects gas and oil movement; a sudden pressure relay responds to rapid tank pressure rise.
Read the source: ETR-4000 and ETR-5000 transformer protection function tables · IEC graphical symbols for diagrams
A Buchholz relay is fitted in the pipe between an oil-filled transformer tank and its conservator. Slow gas accumulation from minor internal faults operates an alarm float, while a rapid surge of oil from a serious internal fault operates a trip element, so the schematic shows two separate contacts.
On single-line diagrams it may appear only as a label on the transformer, while the control schematic shows its alarm and trip contacts wired to annunciation and the transformer trip relay. The symbol does not show the gas sampling procedure or the test arrangement used during maintenance.
A Buchholz relay detects gas and oil movement; a sudden pressure relay responds to rapid tank pressure rise.
These public references support the explanation and provide further detail. Their graphics and downloadable files remain with their publishers.
Public transformer protection context in which mechanical transformer protections are wired.
IEC context for graphical symbols used in diagrams; no IEC graphic is reproduced.
This illustration was authored independently by Elora Grid to explain the concept. It is not reproduced from a customer drawing, an official standard graphic or a manufacturer CAD file. Its correspondence to an exact IEC or IEEE symbol identifier has not been certified.
SVG and DXF downloads contain this original artwork. DXF uses unscaled drawing units; a GA envelope supplies no product dimensions, clearances or fabrication information. Original artwork is available under CC BY 4.0. Third-party references retain their own terms.
Elora Grid helps electrical teams work with drawings, specifications and equipment information. Explore the drafting workflow or join the early-access waitlist.