Rate-of-rise heat detector plan symbol
Fire alarm plan symbol for a heat detector that alarms on a rapid temperature increase as well as a threshold.
Fire alarm plan symbol for a fixed-temperature heat detector that alarms at a set temperature.
In plain English
Fixed-temperature heat detectors alarm when the surrounding air reaches a set point, commonly around 57 to 90 degrees Celsius depending on class. Plans draw the detector box with a temperature mark or the letter H, often with a class tag.
They are used where smoke detectors would false alarm, such as kitchens, plant rooms, car parks and dusty areas. The detection is slower than smoke, so coverage spacing is tighter and the reason for choosing heat should be clear. The symbol does not give the operating temperature or class. Check the schedule, especially in hot plant rooms.
Confirm the class suits the ambient temperature. Check spacing, which is tighter than for smoke. A rate-of-rise detector responds to a fast temperature increase; this one only to an absolute threshold.
Fire alarm plan symbol for a fixed-temperature heat detector that alarms at a set temperature. A rate-of-rise detector responds to a fast temperature increase; this one only to an absolute threshold.
Read the source: IEC graphical symbols for diagrams · Electrical installation design methodology and references
IEC 60617 installation-plan style (architectural and topographical installation symbols); independently drawn, not certified IEC geometry or a database identifier.
Shown as an independently authored educational illustration. Use the cited publication and drawing legend to verify the required drafting form.
Fixed-temperature heat detectors alarm when the surrounding air reaches a set point, commonly around 57 to 90 degrees Celsius depending on class. Plans draw the detector box with a temperature mark or the letter H, often with a class tag.
They are used where smoke detectors would false alarm, such as kitchens, plant rooms, car parks and dusty areas. The detection is slower than smoke, so coverage spacing is tighter and the reason for choosing heat should be clear. The symbol does not give the operating temperature or class. Check the schedule, especially in hot plant rooms.
A rate-of-rise detector responds to a fast temperature increase; this one only to an absolute threshold.
These public references support the explanation and provide further detail. Their graphics and downloadable files remain with their publishers.
IEC graphical symbol context for installation plans; independently drawn here.
Installation design context: life-safety systems are coordinated with the building electrical design.