Switch-disconnector
A switch-disconnector combines operational switching with an isolation function.
Plan mark for a local isolating switch placed beside fixed equipment for safe maintenance.
In plain English
Local isolators are placed within sight of motors, air-conditioning units, pumps and fans so maintenance staff can isolate and lock the supply. Plans draw a small switch box with an isolation mark or the letters ISO beside the equipment it serves, sometimes with a lock indication.
The mark tells the installer to provide a device rated for isolation and, where required, lockable in the off position. Pole count follows the supply: three-pole or four-pole for three-phase plant. It does not specify utilisation category or whether the device can switch motor load. Those are in the schedule.
Check it is within sight of the equipment. Confirm pole count and locking provision. A switched socket outlet is not an isolator; this plan mark designates an isolation-rated device.
Plan mark for a local isolating switch placed beside fixed equipment for safe maintenance. A switched socket outlet is not an isolator; this plan mark designates an isolation-rated device.
Read the source: IEC graphical symbols for diagrams · Elementary switching devices
IEC 60617 installation-plan style (architectural and topographical installation symbols); independently drawn, not certified IEC geometry or a database identifier.
Shown as an independently authored educational illustration. Use the cited publication and drawing legend to verify the required drafting form.
Local isolators are placed within sight of motors, air-conditioning units, pumps and fans so maintenance staff can isolate and lock the supply. Plans draw a small switch box with an isolation mark or the letters ISO beside the equipment it serves, sometimes with a lock indication.
The mark tells the installer to provide a device rated for isolation and, where required, lockable in the off position. Pole count follows the supply: three-pole or four-pole for three-phase plant. It does not specify utilisation category or whether the device can switch motor load. Those are in the schedule.
A switched socket outlet is not an isolator; this plan mark designates an isolation-rated device.
These public references support the explanation and provide further detail. Their graphics and downloadable files remain with their publishers.
IEC graphical symbol context; independently drawn here.
Explains the isolation function and its requirements.
This illustration was authored independently by Elora Grid to explain the concept. It is not reproduced from a customer drawing, an official standard graphic or a manufacturer CAD file. Its correspondence to an exact IEC or IEEE symbol identifier has not been certified.
SVG and DXF downloads contain this original artwork. DXF uses unscaled drawing units; a GA envelope supplies no product dimensions, clearances or fabrication information. Original artwork is available under CC BY 4.0. Third-party references retain their own terms.