Symbols · TCS

Trip-circuit supervision relay

Relay that passes a small current through the trip circuit to check continuity and alarms if the circuit is broken.

In plain English

What does Trip-circuit supervision relay mean?

A trip-circuit supervision relay monitors the wiring, auxiliary contacts and trip coil of a circuit breaker by passing a current too small to trip it. If the trip circuit is broken or its supply fails, the relay drops out and raises an alarm, so a failed trip path is found before a fault needs it.

A simple example

Schemes differ in whether they supervise the circuit with the breaker open and closed, which needs resistors or connections across the breaker auxiliary contacts. The symbol shows the relay but the reader must check which states are actually covered.

Identify the device and formRead the connections and stateCheck the equipment reference
A guide to reading this reference. The original symbol illustration and its drawing notes appear below; these boxes are not a wiring diagram.

What the drawings help you do

Check supervision covers both breaker positions. Verify the supervision current cannot operate the trip coil. Trip-circuit supervision monitors trip path continuity; a lockout relay latches after a trip.

This particular reference

Relay that passes a small current through the trip circuit to check continuity and alarms if the circuit is broken. Trip-circuit supervision monitors trip path continuity; a lockout relay latches after a trip.

Normally open / normally closed
The contact state in the normal condition defined for the drawing.
Coil
A wound conductor that can produce a magnetic field when energised.
Terminal
An identified point where a conductor connects.

Read the source: Relion 620: functions, codes and symbols · IEC graphical symbols for diagrams

Schematic · TCSTrip-circuit supervision relay: original educational illustration
Original educational illustrationNot to scale · See source and graphic notes

What it represents

A trip-circuit supervision relay monitors the wiring, auxiliary contacts and trip coil of a circuit breaker by passing a current too small to trip it. If the trip circuit is broken or its supply fails, the relay drops out and raises an alarm, so a failed trip path is found before a fault needs it.

Schemes differ in whether they supervise the circuit with the breaker open and closed, which needs resistors or connections across the breaker auxiliary contacts. The symbol shows the relay but the reader must check which states are actually covered.

How to read it

  • Check supervision covers both breaker positions.
  • Verify the supervision current cannot operate the trip coil.

Information to show or reference

  • Show connections across trip contacts
  • State supervised breaker states
  • Reference alarm output

A distinction that matters

Trip-circuit supervision monitors trip path continuity; a lockout relay latches after a trip.

Sources you can follow

These public references support the explanation and provide further detail. Their graphics and downloadable files remain with their publishers.

Relion 620: functions, codes and symbols

Public relay function list including trip-circuit supervision.

ABB · Public reference checked 13 October 2026 · Link only

IEC graphical symbols for diagrams

IEC context for graphical symbols used in diagrams; no IEC graphic is reproduced.

IEC · Public reference checked 13 October 2026 · Link only

About this graphic

This illustration was authored independently by Elora Grid to explain the concept. It is not reproduced from a customer drawing, an official standard graphic or a manufacturer CAD file. Its correspondence to an exact IEC or IEEE symbol identifier has not been certified.

SVG and DXF downloads contain this original artwork. DXF uses unscaled drawing units; a GA envelope supplies no product dimensions, clearances or fabrication information. Original artwork is available under CC BY 4.0. Third-party references retain their own terms.

Entry JSON · Entry Markdown · Last editorial update: 28 October 2026

Put the reference into a drawing workflow.

Elora Grid helps electrical teams work with drawings, specifications and equipment information. Explore the drafting workflow or join the early-access waitlist.

Explore drafting