Side-by-side reference

Understand the difference.

Compare the meaning, drawing context and source references of two entries. A similar graphic or shared abbreviation does not establish equivalence.

KEarth-fault current relay: original educational illustration
Symbols

Earth-fault current relay

The earth-fault current relay form identifies a relay whose operating quantity is current flowing to earth. It may be fed from a core-balance CT around all live conductors, from the residual connection of three phase CTs, or from a CT in the star-point earth lead, and the source changes its achievable sensitivity.

Drawing use
Schematic / SLD
Application
Metering & protection
Reference family
IEC / Manufacturer

A distinction that matters

An earth-fault current relay measures current to earth; an earth-fault voltage relay measures neutral displacement voltage.

Full reference
CBCTCore-balance current transformer: original educational illustration
Symbols

Core-balance current transformer

A core-balance CT measures residual current from the net magnetic effect of conductors passing through its window. It is used with earth-fault protection where the conductor arrangement and sheath routing affect the measurement.

Drawing use
SLD / Schematic
Application
Metering & protection
Reference family
IEC / Manufacturer

A distinction that matters

A CBCT measures a combined residual quantity; a phase CT measures an individual conductor current.

Full reference

Original educational previews. Follow the source references on each full entry for the appropriate standard or selected product.

Compare electrical drawing references | Elora Grid