Understand the difference.

Compare the meaning, drawing context and source references of two entries. A similar graphic or shared abbreviation does not establish equivalence.

UPS VILine-interactive UPS: original educational illustration
Symbols

Line-interactive UPS

A line-interactive UPS supplies the load from mains in normal operation, using an automatic voltage regulation stage, often a tapped autotransformer, to correct sags and swells. One bidirectional converter charges the battery while mains is present and inverts from the battery when mains fails, with a short transfer of a few milliseconds.

Drawing use
SLD
Application
Microgrid systems
Reference family
IEC / IEEE / ANSI

A distinction that matters

A line-interactive UPS corrects voltage on the mains path; an offline UPS passes mains without correction until it transfers.

Full reference
UPS VFIOnline double-conversion UPS: original educational illustration
Symbols

Online double-conversion UPS

In an online double-conversion UPS the load is always supplied by the inverter. The rectifier converts incoming AC to DC, the battery floats on the DC link, and the inverter produces a regulated output that is independent of input voltage and frequency variations. When the input fails, the battery simply takes over the DC link with no transfer.

Drawing use
SLD
Application
Microgrid systems
Reference family
IEC / IEEE / ANSI

A distinction that matters

An online UPS powers the load through the inverter all the time; a line-interactive UPS passes mains to the load and only inverts during disturbances.

Full reference