Neutral-to-earth link
The single link bonding the neutral bar to the earth bar at the point where a TN-C-S supply splits into N and PE.
US-practice bonding jumper between the grounded neutral and the equipment grounding system at the service.
In plain English
In North American practice the main bonding jumper connects the grounded conductor, the neutral, to the equipment grounding conductor and enclosure at the service equipment. Its function corresponds to the neutral-to-earth link in TN-C-S systems. Single-line diagrams show it at the service disconnect, and separately derived systems have a corresponding system bonding jumper.
This illustration is an independent explanation and not an IEEE graphic. Only one bond should exist per service or separately derived system. Sizing rules come from the applicable electrical code, and the drawing should state the conductor or strap size.
Locate the bond at the service or derived system source only. Check for unwanted downstream neutral to ground bonds. A main bonding jumper bonds neutral and ground at the service; an equipment bonding jumper bonds metal parts together.
US-practice bonding jumper between the grounded neutral and the equipment grounding system at the service. A main bonding jumper bonds neutral and ground at the service; an equipment bonding jumper bonds metal parts together.
Read the source: IEEE/ANSI 315-1975: graphic symbols for electrical and electronics diagrams · Autodesk IEEE Symbol Preview — Miscellaneous
Independent illustration in IEEE drafting context; no equivalence of every detailed standard graphic is asserted.
Shown as an independently authored educational illustration. Use the cited publication and drawing legend to verify the required drafting form.
In North American practice the main bonding jumper connects the grounded conductor, the neutral, to the equipment grounding conductor and enclosure at the service equipment. Its function corresponds to the neutral-to-earth link in TN-C-S systems. Single-line diagrams show it at the service disconnect, and separately derived systems have a corresponding system bonding jumper.
This illustration is an independent explanation and not an IEEE graphic. Only one bond should exist per service or separately derived system. Sizing rules come from the applicable electrical code, and the drawing should state the conductor or strap size.
A main bonding jumper bonds neutral and ground at the service; an equipment bonding jumper bonds metal parts together.
These public references support the explanation and provide further detail. Their graphics and downloadable files remain with their publishers.
Graphic-symbol standards context and official status; not a source of reproduced artwork.
Public IEEE-oriented earth and bonding forms.
This illustration was authored independently by Elora Grid to explain the concept. It is not reproduced from a customer drawing, an official standard graphic or a manufacturer CAD file. Its correspondence to an exact IEC or IEEE symbol identifier has not been certified.
SVG and DXF downloads contain this original artwork. DXF uses unscaled drawing units; a GA envelope supplies no product dimensions, clearances or fabrication information. Original artwork is available under CC BY 4.0. Third-party references retain their own terms.
Elora Grid helps electrical teams work with drawings, specifications and equipment information. Explore the drafting workflow or join the early-access waitlist.