PEN conductor mark
A mark identifying a combined protective and neutral conductor, as used in TN-C sections of a supply.
The single link bonding the neutral bar to the earth bar at the point where a TN-C-S supply splits into N and PE.
In plain English
The neutral-to-earth link connects the neutral and earth bars at one point, normally the main switchboard. In Australian and New Zealand practice it is the MEN link, and in other TN-C-S schemes it is the point where the incoming PEN is split. It provides the low impedance path that lets earth faults operate overcurrent devices.
There must be only one such link in an installation section. A second neutral to earth bond downstream creates parallel neutral current in earthing conductors and can defeat residual current devices. The symbol does not show the conductor size of the link, which local rules set.
Confirm there is only one neutral to earth link in the installation section. Check RCD-protected circuits downstream for unintended bonds. The neutral-to-earth link bonds N and PE in service; the earth test link is opened only to test the electrode.
The single link bonding the neutral bar to the earth bar at the point where a TN-C-S supply splits into N and PE. The neutral-to-earth link bonds N and PE in service; the earth test link is opened only to test the electrode.
Read the source: Definition of standardised earthing schemes · Earthing connections
Independent IEC-context illustration; not certified IEC geometry.
Shown as an independently authored educational illustration. Use the cited publication and drawing legend to verify the required drafting form.
The neutral-to-earth link connects the neutral and earth bars at one point, normally the main switchboard. In Australian and New Zealand practice it is the MEN link, and in other TN-C-S schemes it is the point where the incoming PEN is split. It provides the low impedance path that lets earth faults operate overcurrent devices.
There must be only one such link in an installation section. A second neutral to earth bond downstream creates parallel neutral current in earthing conductors and can defeat residual current devices. The symbol does not show the conductor size of the link, which local rules set.
The neutral-to-earth link bonds N and PE in service; the earth test link is opened only to test the electrode.
These public references support the explanation and provide further detail. Their graphics and downloadable files remain with their publishers.
Public installation-guide definitions of TN-C-S schemes and PEN separation.
Public installation-guide earthing connection elements.
This illustration was authored independently by Elora Grid to explain the concept. It is not reproduced from a customer drawing, an official standard graphic or a manufacturer CAD file. Its correspondence to an exact IEC or IEEE symbol identifier has not been certified.
SVG and DXF downloads contain this original artwork. DXF uses unscaled drawing units; a GA envelope supplies no product dimensions, clearances or fabrication information. Original artwork is available under CC BY 4.0. Third-party references retain their own terms.
Elora Grid helps electrical teams work with drawings, specifications and equipment information. Explore the drafting workflow or join the early-access waitlist.