IEC · MEN

Neutral-to-earth link

The single link bonding the neutral bar to the earth bar at the point where a TN-C-S supply splits into N and PE.

In plain English

What does Neutral-to-earth link mean?

The neutral-to-earth link connects the neutral and earth bars at one point, normally the main switchboard. In Australian and New Zealand practice it is the MEN link, and in other TN-C-S schemes it is the point where the incoming PEN is split. It provides the low impedance path that lets earth faults operate overcurrent devices.

A simple example

There must be only one such link in an installation section. A second neutral to earth bond downstream creates parallel neutral current in earthing conductors and can defeat residual current devices. The symbol does not show the conductor size of the link, which local rules set.

Identify the device and formRead the connections and stateCheck the equipment reference
A guide to reading this reference. The original symbol illustration and its drawing notes appear below; these boxes are not a wiring diagram.

What the drawings help you do

Confirm there is only one neutral to earth link in the installation section. Check RCD-protected circuits downstream for unintended bonds. The neutral-to-earth link bonds N and PE in service; the earth test link is opened only to test the electrode.

This particular reference

The single link bonding the neutral bar to the earth bar at the point where a TN-C-S supply splits into N and PE. The neutral-to-earth link bonds N and PE in service; the earth test link is opened only to test the electrode.

Rating
A value stating the conditions for which equipment is specified.
Schematic
A drawing showing function and connections rather than physical appearance.

Read the source: Definition of standardised earthing schemes · Earthing connections

IEC · Neutral to earth bonding link

Independent IEC-context illustration; not certified IEC geometry.

Shown as an independently authored educational illustration. Use the cited publication and drawing legend to verify the required drafting form.

SLD / Schematic · MENNeutral-to-earth link: original educational illustration
Original educational illustrationNot to scale · See source and graphic notes

What it represents

The neutral-to-earth link connects the neutral and earth bars at one point, normally the main switchboard. In Australian and New Zealand practice it is the MEN link, and in other TN-C-S schemes it is the point where the incoming PEN is split. It provides the low impedance path that lets earth faults operate overcurrent devices.

There must be only one such link in an installation section. A second neutral to earth bond downstream creates parallel neutral current in earthing conductors and can defeat residual current devices. The symbol does not show the conductor size of the link, which local rules set.

How to read it

  • Confirm there is only one neutral to earth link in the installation section.
  • Check RCD-protected circuits downstream for unintended bonds.

Information to show or reference

  • Show the link at the main switchboard.
  • State link conductor size.
  • Avoid any downstream neutral to earth bond.

A distinction that matters

The neutral-to-earth link bonds N and PE in service; the earth test link is opened only to test the electrode.

Sources you can follow

These public references support the explanation and provide further detail. Their graphics and downloadable files remain with their publishers.

Definition of standardised earthing schemes

Public installation-guide definitions of TN-C-S schemes and PEN separation.

Schneider Electric, Electrical Installation Guide · Public reference checked 28 October 2026 · Link only

Earthing connections

Public installation-guide earthing connection elements.

Schneider Electric, Electrical Installation Guide · Public reference checked 28 October 2026 · Link only

About this graphic

This illustration was authored independently by Elora Grid to explain the concept. It is not reproduced from a customer drawing, an official standard graphic or a manufacturer CAD file. Its correspondence to an exact IEC or IEEE symbol identifier has not been certified.

SVG and DXF downloads contain this original artwork. DXF uses unscaled drawing units; a GA envelope supplies no product dimensions, clearances or fabrication information. Original artwork is available under CC BY 4.0. Third-party references retain their own terms.

Entry JSON · Entry Markdown · Last editorial update: 28 October 2026

Put the reference into a drawing workflow.

Elora Grid helps electrical teams work with drawings, specifications and equipment information. Explore the drafting workflow or join the early-access waitlist.

Explore drafting