ANSI/IEEE Neutral-current measuring relay form

IEEE-library form of neutral-current measuring relay: measuring relay fed from a CT in a neutral conductor or star-point connection, responding to neutral current.

In plain English

What does ANSI/IEEE Neutral-current measuring relay form mean?

This reference locates neutral-current measuring relay in Autodesk's IEEE-oriented current protection relays family. This relay form is used where a CT is installed in a neutral conductor or in the earthing connection of a transformer or generator star point. Current there indicates earth faults or, in four-wire systems, heavy unbalance and triplen harmonic loading, depending on where the CT sits. The public library uses HCR1F32 for its horizontal representation; this is a vendor block name, not an IEEE standards symbol number.

A simple example

Trace the measured quantity or initiating control signal separately from the output contacts. The device tag links the sensing or operating element to the controlled circuit; settings, reset behaviour and the actual terminal arrangement belong in the selected equipment documentation.

Identify the device and formRead the connections and stateCheck the equipment reference
A guide to reading this reference. The original symbol illustration and its drawing notes appear below; these boxes are not a wiring diagram.

What the drawings help you do

The symbol identifies the measured conductor but not the purpose. A neutral CT in the star-point earth lead gives standby earth-fault protection, while one in the four-wire neutral of a feeder sees load unbalance as well, so settings and grading differ greatly. Confirm whether the CT is in the neutral conductor or the earthing lead. A neutral-current relay measures one neutral path; a residual connection sums the three phase CTs to derive the same quantity. The linked functional counterpart explains the same operating role in its own drawing context; agreement of every detailed convention mark is not asserted.

This particular reference

IEEE-library form of neutral-current measuring relay: measuring relay fed from a CT in a neutral conductor or star-point connection, responding to neutral current. A neutral-current relay measures one neutral path; a residual connection sums the three phase CTs to derive the same quantity.

Winding
A coil of conductor inside an electrical machine or transformer.
Normally open / normally closed
The contact state in the normal condition defined for the drawing.
Coil
A wound conductor that can produce a magnetic field when energised.

Read the source: Autodesk IEEE Symbol Preview: Current Protection Relays · IEC graphical symbols for diagrams

IEEE / ANSI · In Neutral

Autodesk IEEE Symbol Preview: Current Protection Relays, block HCR1F32. Matching functional counterpart linked separately. Independently drawn educational geometry; not a certified IEEE glyph or database identifier.

Shown as an independently authored educational illustration. Use the cited publication and drawing legend to verify the required drafting form.

Schematic / SLD · KANSI/IEEE Neutral-current measuring relay form: original educational illustration
Original educational illustrationNot to scale · See source and graphic notes

What it represents

This reference locates neutral-current measuring relay in Autodesk's IEEE-oriented current protection relays family. This relay form is used where a CT is installed in a neutral conductor or in the earthing connection of a transformer or generator star point. Current there indicates earth faults or, in four-wire systems, heavy unbalance and triplen harmonic loading, depending on where the CT sits. The public library uses HCR1F32 for its horizontal representation; this is a vendor block name, not an IEEE standards symbol number.

Trace the measured quantity or initiating control signal separately from the output contacts. The device tag links the sensing or operating element to the controlled circuit; settings, reset behaviour and the actual terminal arrangement belong in the selected equipment documentation.

The symbol identifies the measured conductor but not the purpose. A neutral CT in the star-point earth lead gives standby earth-fault protection, while one in the four-wire neutral of a feeder sees load unbalance as well, so settings and grading differ greatly. Confirm whether the CT is in the neutral conductor or the earthing lead. A neutral-current relay measures one neutral path; a residual connection sums the three phase CTs to derive the same quantity. The linked functional counterpart explains the same operating role in its own drawing context; agreement of every detailed convention mark is not asserted.

How to read it

  • Confirm whether the CT is in the neutral conductor or the earthing lead.
  • Check grading against downstream earth-fault devices.

Information to show or reference

  • Show neutral CT location
  • State setting and delay
  • Reference grading study

A distinction that matters

A neutral-current relay measures one neutral path; a residual connection sums the three phase CTs to derive the same quantity.

Sources you can follow

These public references support the explanation and provide further detail. Their graphics and downloadable files remain with their publishers.

Autodesk IEEE Symbol Preview: Current Protection Relays

Public IEEE-oriented Current Protection Relays table explicitly lists HCR1F32 as In Neutral. This supports the vendor convention context, not reproduction of the publisher graphic.

Autodesk · Public reference checked 28 October 2026 · Link only

IEC graphical symbols for diagrams

IEC context for graphical symbols used in diagrams; no IEC graphic is reproduced.

IEC · Public reference checked 13 October 2026 · Link only

About this graphic

This illustration was authored independently by Elora Grid to explain the concept. It is not reproduced from a customer drawing, an official standard graphic or a manufacturer CAD file. Its correspondence to an exact IEC or IEEE symbol identifier has not been certified.

SVG and DXF downloads contain this original artwork. DXF uses unscaled drawing units; a GA envelope supplies no product dimensions, clearances or fabrication information. Original artwork is available under CC BY 4.0. Third-party references retain their own terms.

Entry JSON · Entry Markdown · Last editorial update: 28 October 2026

Put the reference into a drawing workflow.

Elora Grid helps electrical teams work with drawings, specifications and equipment information. Explore the drafting workflow or join the early-access waitlist.

Explore drafting