ANSI/IEEE Neutral-unbalance relay between two polyphase systems form

IEEE-library reference for neutral-unbalance relay between two polyphase systems, with its operating meaning, connection notes and public vendor block identity.

In plain English

What does ANSI/IEEE Neutral-unbalance relay between two polyphase systems form mean?

This reference locates neutral-unbalance relay between two polyphase systems in Autodesk's IEEE-oriented current protection relays family. This form shows a current relay in the conductor that joins the neutral points of two star-connected polyphase systems. A familiar application is the double-star capacitor bank, where a CT in the link between the two star points detects unbalance caused by failed capacitor units. The public library uses HCR1F33 for its horizontal representation; this is a vendor block name, not an IEEE standards symbol number.

A simple example

Trace the measured quantity or initiating control signal separately from the output contacts. The device tag links the sensing or operating element to the controlled circuit; settings, reset behaviour and the actual terminal arrangement belong in the selected equipment documentation.

Identify the device and formRead the connections and stateCheck the equipment reference
A guide to reading this reference. The original symbol illustration and its drawing notes appear below; these boxes are not a wiring diagram.

What the drawings help you do

In a healthy balanced arrangement the link carries little current, so the relay setting is a small fraction of phase current and must allow for natural unbalance. The symbol does not tell you the alarm and trip stages or the compensation for inherent unbalance; those are in the bank protection settings. Identify the two star points joined by the measured link. This relay measures the link between two star points; a neutral-current relay measures one neutral path to earth or to the supply. The linked functional counterpart explains the same operating role in its own drawing context; agreement of every detailed convention mark is not asserted.

This particular reference

IEEE-library reference for neutral-unbalance relay between two polyphase systems, with its operating meaning, connection notes and public vendor block identity. This relay measures the link between two star points; a neutral-current relay measures one neutral path to earth or to the supply.

Normally open / normally closed
The contact state in the normal condition defined for the drawing.
Coil
A wound conductor that can produce a magnetic field when energised.
Phase
One of the related AC waveforms in a power system.

Read the source: Autodesk IEEE Symbol Preview: Current Protection Relays · IEC graphical symbols for diagrams

IEEE / ANSI · In Neutral between 2 Multi-Phase Systems

Autodesk IEEE Symbol Preview: Current Protection Relays, block HCR1F33. Matching functional counterpart linked separately. Independently drawn educational geometry; not a certified IEEE glyph or database identifier.

Shown as an independently authored educational illustration. Use the cited publication and drawing legend to verify the required drafting form.

Schematic / SLD · KANSI/IEEE Neutral-unbalance relay between two polyphase systems form: original educational illustration
Original educational illustrationNot to scale · See source and graphic notes

What it represents

This reference locates neutral-unbalance relay between two polyphase systems in Autodesk's IEEE-oriented current protection relays family. This form shows a current relay in the conductor that joins the neutral points of two star-connected polyphase systems. A familiar application is the double-star capacitor bank, where a CT in the link between the two star points detects unbalance caused by failed capacitor units. The public library uses HCR1F33 for its horizontal representation; this is a vendor block name, not an IEEE standards symbol number.

Trace the measured quantity or initiating control signal separately from the output contacts. The device tag links the sensing or operating element to the controlled circuit; settings, reset behaviour and the actual terminal arrangement belong in the selected equipment documentation.

In a healthy balanced arrangement the link carries little current, so the relay setting is a small fraction of phase current and must allow for natural unbalance. The symbol does not tell you the alarm and trip stages or the compensation for inherent unbalance; those are in the bank protection settings. Identify the two star points joined by the measured link. This relay measures the link between two star points; a neutral-current relay measures one neutral path to earth or to the supply. The linked functional counterpart explains the same operating role in its own drawing context; agreement of every detailed convention mark is not asserted.

How to read it

  • Identify the two star points joined by the measured link.
  • Look for separate alarm and trip stages.

Information to show or reference

  • Show the interconnecting link and CT
  • State alarm and trip settings
  • Note inherent unbalance compensation

A distinction that matters

This relay measures the link between two star points; a neutral-current relay measures one neutral path to earth or to the supply.

Sources you can follow

These public references support the explanation and provide further detail. Their graphics and downloadable files remain with their publishers.

Autodesk IEEE Symbol Preview: Current Protection Relays

Public IEEE-oriented Current Protection Relays table explicitly lists HCR1F33 as In Neutral between 2 Multi-Phase Systems. This supports the vendor convention context, not reproduction of the publisher graphic.

Autodesk · Public reference checked 28 October 2026 · Link only

IEC graphical symbols for diagrams

IEC context for graphical symbols used in diagrams; no IEC graphic is reproduced.

IEC · Public reference checked 13 October 2026 · Link only

About this graphic

This illustration was authored independently by Elora Grid to explain the concept. It is not reproduced from a customer drawing, an official standard graphic or a manufacturer CAD file. Its correspondence to an exact IEC or IEEE symbol identifier has not been certified.

SVG and DXF downloads contain this original artwork. DXF uses unscaled drawing units; a GA envelope supplies no product dimensions, clearances or fabrication information. Original artwork is available under CC BY 4.0. Third-party references retain their own terms.

Entry JSON · Entry Markdown · Last editorial update: 28 October 2026