Screened conductor
A single conductor enclosed by a drawn screen outline, showing that the core has a conductive shield around it.
IEEE-oriented shielded conductor drawn with a dashed or broken outline around the wire to show a shield.
In plain English
In IEEE-oriented drawings a shielded conductor is commonly shown with a broken or dashed enclosure around the conductor, sometimes with a short lead to a ground symbol. US instrumentation drawings use it for analogue signal wiring, thermocouple extension leads and drive feedback.
This is an independently drawn explanation of the convention, not a reproduction of the IEEE graphic. As with the IEC form, the outline does not say where the shield is grounded, which must be shown at the shield lead. Shield drain wires should have their own terminal numbers.
Locate the shield drain termination. Check whether the shield is grounded at one end only. A shielded conductor intercepts interference; a coaxial cable uses its outer conductor as the signal return.
IEEE-oriented shielded conductor drawn with a dashed or broken outline around the wire to show a shield. A shielded conductor intercepts interference; a coaxial cable uses its outer conductor as the signal return.
Read the source: IEEE/ANSI 315-1975: graphic symbols for electrical and electronics diagrams · Autodesk IEEE Symbol Preview — Miscellaneous
Independent illustration in IEEE drafting context; no equivalence of every detailed standard graphic is asserted.
Shown as an independently authored educational illustration. Use the cited publication and drawing legend to verify the required drafting form.
In IEEE-oriented drawings a shielded conductor is commonly shown with a broken or dashed enclosure around the conductor, sometimes with a short lead to a ground symbol. US instrumentation drawings use it for analogue signal wiring, thermocouple extension leads and drive feedback.
This is an independently drawn explanation of the convention, not a reproduction of the IEEE graphic. As with the IEC form, the outline does not say where the shield is grounded, which must be shown at the shield lead. Shield drain wires should have their own terminal numbers.
A shielded conductor intercepts interference; a coaxial cable uses its outer conductor as the signal return.
These public references support the explanation and provide further detail. Their graphics and downloadable files remain with their publishers.
Graphic-symbol standards context and official status; not a source of reproduced artwork.
Public IEEE-oriented earth forms used on shield drains.
This illustration was authored independently by Elora Grid to explain the concept. It is not reproduced from a customer drawing, an official standard graphic or a manufacturer CAD file. Its correspondence to an exact IEC or IEEE symbol identifier has not been certified.
SVG and DXF downloads contain this original artwork. DXF uses unscaled drawing units; a GA envelope supplies no product dimensions, clearances or fabrication information. Original artwork is available under CC BY 4.0. Third-party references retain their own terms.
Elora Grid helps electrical teams work with drawings, specifications and equipment information. Explore the drafting workflow or join the early-access waitlist.