Screened conductor with earthed screen
A screened conductor whose screen tail is drawn to an earth symbol, recording where the shield is earthed.
A single conductor enclosed by a drawn screen outline, showing that the core has a conductive shield around it.
In plain English
A screened conductor symbol adds an outline around one conductor to show a conductive screen, braid or foil surrounding the core. It is used for analogue instrument signals, encoder and thermocouple extension wiring and other circuits where capacitively coupled interference must be kept off the signal.
The outline alone does not show where or whether the screen is earthed. Earthing at one end, both ends or through a capacitor is a design decision that should be drawn explicitly with an earth or bonding symbol at the screen tail. The symbol also does not distinguish foil, braid or combined screens, which belong in the cable schedule.
Find the screen tail and confirm where it is terminated. Check whether a cable marker applies to the screened core and any others in the same cable. A screened conductor has a conductive shield; a cable-core grouping outline only shows that several cores share one sheath and implies no shielding.
A single conductor enclosed by a drawn screen outline, showing that the core has a conductive shield around it. A screened conductor has a conductive shield; a cable-core grouping outline only shows that several cores share one sheath and implies no shielding.
Read the source: Autodesk IEC-60617 preview: Cable identification and twisted-pair annotation · IEC-60617 symbol preview directory
Independent IEC-context illustration; consult IEC 60617 for the exact screen outline.
Shown as an independently authored educational illustration. Use the cited publication and drawing legend to verify the required drafting form.
A screened conductor symbol adds an outline around one conductor to show a conductive screen, braid or foil surrounding the core. It is used for analogue instrument signals, encoder and thermocouple extension wiring and other circuits where capacitively coupled interference must be kept off the signal.
The outline alone does not show where or whether the screen is earthed. Earthing at one end, both ends or through a capacitor is a design decision that should be drawn explicitly with an earth or bonding symbol at the screen tail. The symbol also does not distinguish foil, braid or combined screens, which belong in the cable schedule.
A screened conductor has a conductive shield; a cable-core grouping outline only shows that several cores share one sheath and implies no shielding.
These public references support the explanation and provide further detail. Their graphics and downloadable files remain with their publishers.
Public IEC-60617 preview family for cable annotation used alongside screened-core forms.
Public directory of IEC-oriented symbol families.
This illustration was authored independently by Elora Grid to explain the concept. It is not reproduced from a customer drawing, an official standard graphic or a manufacturer CAD file. Its correspondence to an exact IEC or IEEE symbol identifier has not been certified.
SVG and DXF downloads contain this original artwork. DXF uses unscaled drawing units; a GA envelope supplies no product dimensions, clearances or fabrication information. Original artwork is available under CC BY 4.0. Third-party references retain their own terms.
Elora Grid helps electrical teams work with drawings, specifications and equipment information. Explore the drafting workflow or join the early-access waitlist.