UPS maintenance bypass

An arrangement of interlocked switches that routes the load around a UPS so the UPS can be isolated for work.

In plain English

What does UPS maintenance bypass mean?

A UPS maintenance bypass is a set of switches, usually input, output and bypass, that lets the load be connected directly to the bypass supply while the UPS is fully isolated. It is normally external to the UPS cabinet so that the UPS itself can be removed without disturbing the load wiring.

A simple example

Single-line diagrams show the UPS between an input switch and an output switch, with a bypass switch connecting the input supply directly to the output busbar. Key interlocks or a make-before-break sequence prevent the UPS inverter from being paralleled with an unsynchronised bypass.

Identify the device and formRead the connections and stateCheck the equipment reference
A guide to reading this reference. The original symbol illustration and its drawing notes appear below; these boxes are not a wiring diagram.

What the drawings help you do

The symbol does not tell you the sequence of operation or whether the UPS static bypass must be engaged first. Those steps are critical and must be written on the operating label or switching instruction.

This particular reference

An arrangement of interlocked switches that routes the load around a UPS so the UPS can be isolated for work. A maintenance bypass is external switching around the whole UPS; the static bypass is an internal electronic path.

Signal
Electrical information passed between devices, rather than necessarily the main power supply.
Rating
A value stating the conditions for which equipment is specified.
Schematic
A drawing showing function and connections rather than physical appearance.

Read the source: DC UPS, AC UPS and capacitor buffer modules · IEC graphical symbols for diagrams

SLD · MBPUPS maintenance bypass: original educational illustration
Original educational illustrationNot to scale · See source and graphic notes

What it represents

A UPS maintenance bypass is a set of switches, usually input, output and bypass, that lets the load be connected directly to the bypass supply while the UPS is fully isolated. It is normally external to the UPS cabinet so that the UPS itself can be removed without disturbing the load wiring.

Single-line diagrams show the UPS between an input switch and an output switch, with a bypass switch connecting the input supply directly to the output busbar. Key interlocks or a make-before-break sequence prevent the UPS inverter from being paralleled with an unsynchronised bypass.

The symbol does not tell you the sequence of operation or whether the UPS static bypass must be engaged first. Those steps are critical and must be written on the operating label or switching instruction.

How to read it

  • Identify the three switches and their interlock.
  • The bypass source may differ from the UPS rectifier source.

Information to show or reference

  • State ratings of each switch.
  • Show interlocks.
  • Reference operating sequence.

A distinction that matters

A maintenance bypass is external switching around the whole UPS; the static bypass is an internal electronic path.

Sources you can follow

These public references support the explanation and provide further detail. Their graphics and downloadable files remain with their publishers.

DC UPS, AC UPS and capacitor buffer modules

Public UPS function context.

Phoenix Contact · Public reference checked 13 October 2026 · Link only

IEC graphical symbols for diagrams

IEC graphical symbol context for switches.

IEC · Public reference checked 13 October 2026 · Link only

About this graphic

This illustration was authored independently by Elora Grid to explain the concept. It is not reproduced from a customer drawing, an official standard graphic or a manufacturer CAD file. Its correspondence to an exact IEC or IEEE symbol identifier has not been certified.

SVG and DXF downloads contain this original artwork. DXF uses unscaled drawing units; a GA envelope supplies no product dimensions, clearances or fabrication information. Original artwork is available under CC BY 4.0. Third-party references retain their own terms.

Entry JSON · Entry Markdown · Last editorial update: 28 October 2026

Put the reference into a drawing workflow.

Elora Grid helps electrical teams work with drawings, specifications and equipment information. Explore the drafting workflow or join the early-access waitlist.

Explore drafting