Side-by-side reference

Understand the difference.

Compare the meaning, drawing context and source references of two entries. A similar graphic or shared abbreviation does not establish equivalence.

MENNeutral-to-earth link: original educational illustration
IEC

Neutral-to-earth link

The neutral-to-earth link connects the neutral and earth bars at one point, normally the main switchboard. In Australian and New Zealand practice it is the MEN link, and in other TN-C-S schemes it is the point where the incoming PEN is split. It provides the low impedance path that lets earth faults operate overcurrent devices.

Drawing use
SLD / Schematic
Application
Connections & wiring
Reference family
IEC
Form evidence
Neutral to earth bonding link. Independent IEC-context illustration; not certified IEC geometry.

A distinction that matters

The neutral-to-earth link bonds N and PE in service; the earth test link is opened only to test the electrode.

Full reference
PENPEN conductor mark: original educational illustration
IEC

PEN conductor mark

The PEN mark identifies one conductor that performs both the protective and neutral functions. It appears in TN-C and TN-C-S arrangements, typically between the supply transformer and the main switchboard, where the PEN is later separated into N and PE at a defined point.

Drawing use
SLD / Schematic
Application
Connections & wiring
Reference family
IEC
Form evidence
PEN conductor identification on a conductor group. Independent IEC-context illustration; not certified IEC geometry.

A distinction that matters

A PEN conductor combines N and PE functions; a neutral mark shows a conductor that has no protective role.

Full reference

Original educational previews. Follow the source references on each full entry for the appropriate standard or selected product.