Side-by-side reference

Understand the difference.

Compare the meaning, drawing context and source references of two entries. A similar graphic or shared abbreviation does not establish equivalence.

32NWattmetric earth-fault protection: original educational illustration
Protection functions

Wattmetric earth-fault protection

Uses residual voltage and current to assess earth-fault power in the documented neutral-system application.

Drawing use
SLD / Schematic
Application
Metering & protection
Reference family
IEEE / ANSI / Manufacturer

A distinction that matters

ABB's 32N mapping identifies wattmetric earth-fault protection; it differs from generator reverse active-power protection.

Full reference
32Directional power: original educational illustration
Protection functions

Directional power

Directional power protection uses the direction and magnitude of power according to the implementation and configured purpose. Reverse-power applications are one use encountered in generating systems; the generic device number does not specify the complete application.

Drawing use
SLD / Schematic
Application
Metering & protection
Reference family
IEEE / ANSI

A distinction that matters

Directional power and directional overcurrent measure different operating quantities. The numbers 32 and 67 are not interchangeable.

Full reference

Original educational previews. Follow the source references on each full entry for the appropriate standard or selected product.