51NTime neutral-overcurrent protection: original educational illustration
Protection functions

Time neutral-overcurrent protection

Supervises neutral or residual overcurrent with the configured timing characteristic.

Drawing use
SLD / Schematic
Application
Metering & protection
Reference family
IEEE / ANSI / Manufacturer

A distinction that matters

Neutral/residual 51N does not determine whether the source is a neutral CT or a residual sum; show the source explicitly.

Full reference
51Time overcurrent: original educational illustration
Protection functions

Time overcurrent

A time overcurrent function detects an overcurrent condition using the configured time characteristic. Depending on the device and application, the implementation can include inverse-time or definite-time behaviour. Its number does not specify a curve, pickup or delay.

Drawing use
SLD / Schematic
Application
Metering & protection
Reference family
IEEE / ANSI

A distinction that matters

Functions 50 and 51 describe different time behaviour. One multifunction relay can implement both without becoming two separate physical devices.

Full reference

Original educational previews. Follow the source references on each full entry for the appropriate standard or selected product.