Compare the meaning, drawing context and source references of two entries. A similar graphic or shared abbreviation does not establish equivalence.

DS AUX NCDisconnector auxiliary NC contact: original educational illustration
Symbols

Disconnector auxiliary NC contact

A normally-closed disconnector auxiliary contact is closed in the documented unactuated reference state. It can be used in indication or interlocking circuits while remaining separate from the main power path.

Drawing use
SLD / Schematic
Application
Power distribution
Reference family
IEC / Manufacturer

A distinction that matters

Normally closed describes a contact state, not the normal operating status of the feeder.

Full reference
IsolatorDisconnector: original educational illustration
Symbols

Disconnector

A disconnector, often called an isolator, provides an isolation function in an electrical circuit. Its representation should be read with the drawing legend and the selected device specification. Do not infer load-breaking or fault-interruption capability simply because a drawing contains a switch-like mark.

Drawing use
SLD / Schematic
Application
Power distribution
Reference family
IEC / IEEE / ANSI

A distinction that matters

A load-break switch has a specified load-switching capability. A disconnector designation alone does not establish that capability.

Full reference

Original educational previews. Follow the source references on each full entry for the appropriate standard or selected product.