NC EARLYEarly-break normally-closed contact: original educational illustration
Symbols

Early-break normally-closed contact

An early-break NC contact opens earlier in a documented mechanical sequence than associated contacts. It may participate in interlocks whose operation depends on this order.

Drawing use
Schematic
Application
Control circuits
Reference family
IEC / Manufacturer

A distinction that matters

Early break is a mechanical sequence annotation, not an instantaneous protection threshold.

Full reference
NONormally open contact: original educational illustration
Symbols

Normally open contact

A normally open contact is open in the normal state defined for the device. Operating its relay, pushbutton or other parent device may close the contact. The meaning of normal must be established from the drawing convention and equipment documentation; it is not necessarily the current live condition of the installation.

Drawing use
Schematic
Application
Control circuits
Reference family
IEC / IEEE / ANSI

A distinction that matters

Normally open describes the stated normal condition. A position indication or operating snapshot may use a different state convention.

Full reference

Original educational previews. Follow the source references on each full entry for the appropriate standard or selected product.