Energy meter repeater
Remote register that counts pulses from a transmitting energy meter and repeats its reading at another location.
Energy meter that sends a pulse output proportional to energy for remote counting, totalising or building management.
In plain English
This form shows an energy meter with a transmitting output, normally a pulse contact where each pulse represents a fixed amount of energy. The output feeds a remote counter, a summation meter, a PLC or a building management system, so the meter symbol is linked to a separate signal circuit.
The pulse weight, such as watt-hours per pulse, and the pulse width are essential for the receiver. The symbol does not show them, and a mismatch between pulse weight and receiver scaling produces errors that are easy to miss.
Record the pulse weight and width. Trace the pulse output to its receiving device. A meter with a transmitter sends its count elsewhere; an energy meter repeater is the receiving remote register.
Energy meter that sends a pulse output proportional to energy for remote counting, totalising or building management. A meter with a transmitter sends its count elsewhere; an energy meter repeater is the receiving remote register.
Read the source: Power and energy measurement quantities · IEC graphical symbols for diagrams
This form shows an energy meter with a transmitting output, normally a pulse contact where each pulse represents a fixed amount of energy. The output feeds a remote counter, a summation meter, a PLC or a building management system, so the meter symbol is linked to a separate signal circuit.
The pulse weight, such as watt-hours per pulse, and the pulse width are essential for the receiver. The symbol does not show them, and a mismatch between pulse weight and receiver scaling produces errors that are easy to miss.
A meter with a transmitter sends its count elsewhere; an energy meter repeater is the receiving remote register.
These public references support the explanation and provide further detail. Their graphics and downloadable files remain with their publishers.
Public explanation of energy and power measurement quantities used by meters.
IEC context for graphical symbols used in diagrams; no IEC graphic is reproduced.
This illustration was authored independently by Elora Grid to explain the concept. It is not reproduced from a customer drawing, an official standard graphic or a manufacturer CAD file. Its correspondence to an exact IEC or IEEE symbol identifier has not been certified.
SVG and DXF downloads contain this original artwork. DXF uses unscaled drawing units; a GA envelope supplies no product dimensions, clearances or fabrication information. Original artwork is available under CC BY 4.0. Third-party references retain their own terms.
Elora Grid helps electrical teams work with drawings, specifications and equipment information. Explore the drafting workflow or join the early-access waitlist.