CT test terminal
A current-transformer terminal arrangement providing documented test and shorting facilities.
Multi-pole test facility between CT, VT and trip wiring and a relay, allowing safe isolation and test injection.
In plain English
A relay test block sits in the secondary wiring between CTs, VTs, trip outputs and a protection relay. Inserting a test plug or opening the block isolates the relay from the plant, automatically shorts CT circuits before they are opened and isolates trip outputs, so the relay can be tested with secondary injection while the primary circuit stays in service.
The schematic should show the order in which poles break and make, because CT shorting must occur before CT circuits open. The symbol alone does not show that sequence, so the terminal arrangement of each pole needs to be drawn or referenced to the manufacturer data.
Check CT poles short before they open. Confirm trip outputs are isolated when the block is opened. A relay test block isolates and shorts circuits in one operation; a single CT test terminal handles only one conductor.
Multi-pole test facility between CT, VT and trip wiring and a relay, allowing safe isolation and test injection. A relay test block isolates and shorts circuits in one operation; a single CT test terminal handles only one conductor.
Read the source: Transformer terminals for measuring and test circuits · Disconnect and knife-disconnect terminal blocks
A relay test block sits in the secondary wiring between CTs, VTs, trip outputs and a protection relay. Inserting a test plug or opening the block isolates the relay from the plant, automatically shorts CT circuits before they are opened and isolates trip outputs, so the relay can be tested with secondary injection while the primary circuit stays in service.
The schematic should show the order in which poles break and make, because CT shorting must occur before CT circuits open. The symbol alone does not show that sequence, so the terminal arrangement of each pole needs to be drawn or referenced to the manufacturer data.
A relay test block isolates and shorts circuits in one operation; a single CT test terminal handles only one conductor.
These public references support the explanation and provide further detail. Their graphics and downloadable files remain with their publishers.
Public manufacturer range of transformer and test terminals for measuring and protection circuits.
Public disconnect and test terminal families used in secondary circuits.
This illustration was authored independently by Elora Grid to explain the concept. It is not reproduced from a customer drawing, an official standard graphic or a manufacturer CAD file. Its correspondence to an exact IEC or IEEE symbol identifier has not been certified.
SVG and DXF downloads contain this original artwork. DXF uses unscaled drawing units; a GA envelope supplies no product dimensions, clearances or fabrication information. Original artwork is available under CC BY 4.0. Third-party references retain their own terms.
Elora Grid helps electrical teams work with drawings, specifications and equipment information. Explore the drafting workflow or join the early-access waitlist.