Neutral link, open
A neutral link drawn removed or open, showing the neutral conductor disconnected at that point.
IEEE-library form of neutral link, open: a neutral link drawn removed or open, showing the neutral conductor disconnected at that point.
In plain English
This reference locates neutral link, open in Autodesk's IEEE-oriented fuses family. The open neutral link shows the link withdrawn so that the neutral is disconnected. Drawings use it where a circuit is normally run with the neutral open, for example to isolate a spare or to segregate a neutral during a changeover, and on test procedures that show the link removed. The public library uses HFU1NLO for its horizontal representation; this is a vendor block name, not an IEEE standards symbol number.
Use the surrounding circuit labels and the project legend to identify the intended operating condition and connection. Carry the same device reference into the schedule or equipment document so the symbol can be reconciled with its real terminals, function and operating limits.
An open neutral on a live four-wire circuit can cause severe overvoltage on single-phase loads, so an open link in normal service needs a clear reason on the drawing. The symbol says nothing about the phase conductors, which may still be supplied with operating power. Ask why the neutral is shown open in service. An open neutral link is disconnected; the closed form shows normal continuity. The linked functional counterpart explains the same operating role in its own drawing context; agreement of every detailed convention mark is not asserted.
IEEE-library form of neutral link, open: a neutral link drawn removed or open, showing the neutral conductor disconnected at that point. An open neutral link is disconnected; the closed form shows normal continuity.
Read the source: Autodesk IEEE Symbol Preview — Fuses · Definition of standardised earthing schemes
Autodesk IEEE Symbol Preview: Fuses, block HFU1NLO. Matching functional counterpart linked separately. Independently drawn educational geometry; not a certified IEEE glyph or database identifier.
Shown as an independently authored educational illustration. Use the cited publication and drawing legend to verify the required drafting form.
This reference locates neutral link, open in Autodesk's IEEE-oriented fuses family. The open neutral link shows the link withdrawn so that the neutral is disconnected. Drawings use it where a circuit is normally run with the neutral open, for example to isolate a spare or to segregate a neutral during a changeover, and on test procedures that show the link removed. The public library uses HFU1NLO for its horizontal representation; this is a vendor block name, not an IEEE standards symbol number.
Use the surrounding circuit labels and the project legend to identify the intended operating condition and connection. Carry the same device reference into the schedule or equipment document so the symbol can be reconciled with its real terminals, function and operating limits.
An open neutral on a live four-wire circuit can cause severe overvoltage on single-phase loads, so an open link in normal service needs a clear reason on the drawing. The symbol says nothing about the phase conductors, which may still be energised. Ask why the neutral is shown open in service. An open neutral link is disconnected; the closed form shows normal continuity. The linked functional counterpart explains the same operating role in its own drawing context; agreement of every detailed convention mark is not asserted.
An open neutral link is disconnected; the closed form shows normal continuity.
These public references support the explanation and provide further detail. Their graphics and downloadable files remain with their publishers.
Public IEEE-oriented Fuses table explicitly lists HFU1NLO as Neutral Link - Open. This supports the vendor convention context, not reproduction of the publisher graphic.
Public installation-guide definitions of the neutral's role in earthing schemes.