Functional block · SDI

Stored-energy discharged indication

Functional block · Switchgear

An independently authored application reference. The drawing shows the named function or circuit relationship; use the project legend and selected equipment documentation for its drafting form and connections.

Browse this installation focus

In plain English

What this block does

Reports the mechanism's documented discharged condition for control or maintenance indication.

A simple example

In a switchgear panel, a charging motor replenishes the mechanism after an operation. Supervisory contacts let the controller report an incomplete charge or repeated charging demand before an operator requests another operation. For this reference, the drawing identifies “Discharged-position contact” at the input and “Stored-energy state” at the output. This signal does not establish all stored energy is absent.

Discharged-position contactSDIStored-energy state
A reading guide. The entry's original illustration and input/output facts describe this application.

What the drawings help you do

Start at the named input: Discharged-position contact. Identify its source device or document and the state represented on the drawing. Follow the named output: Stored-energy state. Cross-reference its destination and separate the command from confirmation that the equipment responded.

Input
Discharged-position contact
Output
Stored-energy state
Application reference
An explanation of a named drawing function or circuit relationship; the project documents define the equipment and its connections.

Read the source: Masterclad medium-voltage switchgear: circuit-breaker section interlocks

Schematic · SDIStored-energy discharged indication: original educational illustration
Original educational illustrationSee source and graphic notes

What it represents

Reports the mechanism's documented discharged condition for control or maintenance indication. A stored-energy breaker mechanism has charging, release, indication and supervision functions. Motor supply, stored spring energy and the ability to complete an opening operation are separate drawing concerns.

In a switchgear panel, a charging motor replenishes the mechanism after an operation. Supervisory contacts let the controller report an incomplete charge or repeated charging demand before an operator requests another operation. For this reference, the drawing identifies “Discharged-position contact” at the input and “Stored-energy state” at the output. This signal does not establish all stored energy is absent.

Show the individual contacts and the relevant motor or release circuit. Supply voltage, charging time, operating duty and permissible alarms must follow the chosen mechanism documentation. The functional block is an independent explanation of this named application. Equipment-specific ratings, terminal connections and operating conditions must be established in the project documentation.

How to read it

  • Start at the named input: Discharged-position contact. Identify its source device or document and the state represented on the drawing.
  • Follow the named output: Stored-energy state. Cross-reference its destination and separate the command from confirmation that the equipment responded.
  • This signal does not establish all stored energy is absent.
  • Show the individual contacts and the relevant motor or release circuit. Supply voltage, charging time, operating duty and permissible alarms must follow the chosen mechanism documentation.

Information to show or reference

  • Label the source and connection reference for discharged-position contact.
  • Identify the destination and defined state of stored-energy state.
  • Record the equipment or control-document revision supporting this functional block.
  • Check this application limit in the project design: This signal does not establish all stored energy is absent.

A distinction that matters

This signal does not establish all stored energy is absent. This reference describes the named application; it does not establish a new IEC graphical symbol, an ANSI device-function number or an exact manufacturer connection diagram.

Sources you can follow

These public references support the explanation and provide further detail. Their graphics and downloadable files remain with their publishers.

Masterclad medium-voltage switchgear: circuit-breaker section interlocks

Public technical context for stored-energy mechanism supervision. Breaker control, mechanism, position contacts, racking interlocks and test interfaces. The application text and educational graphic are independently authored; the publisher does not certify this representation.

Schneider Electric · Public reference checked 3 November 2026 · Link only

About this graphic

This illustration was authored independently by Elora Grid to explain the concept. It is not reproduced from a customer drawing, an official standard graphic or a manufacturer CAD file. Its correspondence to an exact IEC or IEEE symbol identifier has not been certified.