Wound-primary current transformer

CT with a primary winding of several turns, used for low primary currents where a bar primary gives too little accuracy.

In plain English

What does Wound-primary current transformer mean?

A wound-primary CT has a primary winding of more than one turn rather than a single bar or conductor through a window. This is needed at low primary currents, where a single turn would not produce enough magnetising ampere-turns for accurate metering, and it is common in MV metering units.

A simple example

The wound primary has a lower short-time withstand than a bar primary, so its thermal and dynamic ratings need checking against the fault level. The symbol shows the winding but not those ratings, which belong in the CT schedule.

Identify the device and formRead the connections and stateCheck the equipment reference
A guide to reading this reference. The original symbol illustration and its drawing notes appear below; these boxes are not a wiring diagram.

What the drawings help you do

Check the short-time thermal rating against the fault level. Read primary terminals P1 and P2 for polarity. A wound-primary CT has a multi-turn primary; a window or bar CT uses the circuit conductor as a single-turn primary.

This particular reference

CT with a primary winding of several turns, used for low primary currents where a bar primary gives too little accuracy. A wound-primary CT has a multi-turn primary; a window or bar CT uses the circuit conductor as a single-turn primary.

Winding
A coil of conductor inside an electrical machine or transformer.
Rating
A value stating the conditions for which equipment is specified.
Schematic
A drawing showing function and connections rather than physical appearance.

Read the source: Indoor current and voltage transformers · Current transformer symbol variants

SLD / Schematic · CTWound-primary current transformer: original educational illustration
Original educational illustrationNot to scale · See source and graphic notes

What it represents

A wound-primary CT has a primary winding of more than one turn rather than a single bar or conductor through a window. This is needed at low primary currents, where a single turn would not produce enough magnetising ampere-turns for accurate metering, and it is common in MV metering units.

The wound primary has a lower short-time withstand than a bar primary, so its thermal and dynamic ratings need checking against the fault level. The symbol shows the winding but not those ratings, which belong in the CT schedule.

How to read it

  • Check the short-time thermal rating against the fault level.
  • Read primary terminals P1 and P2 for polarity.

Information to show or reference

  • State ratio and class
  • Give short-time rating
  • Show polarity marks

A distinction that matters

A wound-primary CT has a multi-turn primary; a window or bar CT uses the circuit conductor as a single-turn primary.

Sources you can follow

These public references support the explanation and provide further detail. Their graphics and downloadable files remain with their publishers.

Indoor current and voltage transformers

Public manufacturer overview of indoor current and voltage instrument transformers.

ABB · Public reference checked 13 October 2026 · Link only

Current transformer symbol variants

Public AutoCAD Electrical current transformer family used for context; this variant is independently drawn.

Autodesk · Public reference checked 13 October 2026 · Link only

About this graphic

This illustration was authored independently by Elora Grid to explain the concept. It is not reproduced from a customer drawing, an official standard graphic or a manufacturer CAD file. Its correspondence to an exact IEC or IEEE symbol identifier has not been certified.

SVG and DXF downloads contain this original artwork. DXF uses unscaled drawing units; a GA envelope supplies no product dimensions, clearances or fabrication information. Original artwork is available under CC BY 4.0. Third-party references retain their own terms.

Entry JSON · Entry Markdown · Last editorial update: 28 October 2026

Put the reference into a drawing workflow.

Elora Grid helps electrical teams work with drawings, specifications and equipment information. Explore the drafting workflow or join the early-access waitlist.

Explore drafting