Functional block · BEI

Breaker-open earthing interlock

Functional block · Switchgear

An independently authored application reference. The drawing shows the named function or circuit relationship; use the project legend and selected equipment documentation for its drafting form and connections.

Browse this installation focus

In plain English

What this block does

Uses the assigned breaker state as one condition of earthing-switch operation.

A simple example

In a switchgear feeder panel, a control diagram can prevent an incompatible combination of breaker, disconnector and earthing-switch positions. The physical equipment documents determine which restrictions are mechanically enforced. For this reference, the drawing identifies “Breaker open indication” at the input and “Earthing operation condition” at the output. Breaker opening alone does not establish isolation.

Breaker open indicationBEIEarthing operation condition
A reading guide. The entry's original illustration and input/output facts describe this application.

What the drawings help you do

Start at the named input: Breaker open indication. Identify its source device or document and the state represented on the drawing. Follow the named output: Earthing operation condition. Cross-reference its destination and separate the command from confirmation that the equipment responded.

Input
Breaker open indication
Output
Earthing operation condition
Application reference
An explanation of a named drawing function or circuit relationship; the project documents define the equipment and its connections.

Read the source: Masterclad medium-voltage switchgear: circuit-breaker section interlocks

Schematic · BEIBreaker-open earthing interlock: original educational illustration
Original educational illustrationSee source and graphic notes

What it represents

Uses the assigned breaker state as one condition of earthing-switch operation. An interlocking function permits or blocks an operation according to the positions and conditions of related equipment. Electrical, mechanical and trapped-key interlocks implement different parts of a coordinated operating philosophy.

In a switchgear feeder panel, a control diagram can prevent an incompatible combination of breaker, disconnector and earthing-switch positions. The physical equipment documents determine which restrictions are mechanically enforced. For this reference, the drawing identifies “Breaker open indication” at the input and “Earthing operation condition” at the output. Breaker opening alone does not establish isolation.

Identify each initiating position, the action being blocked and the consequence of missing feedback. An illustrative logic diagram must not be treated as an operating procedure or proof of a complete safety system. The functional block is an independent explanation of this named application. Equipment-specific ratings, terminal connections and operating conditions must be established in the project documentation.

How to read it

  • Start at the named input: Breaker open indication. Identify its source device or document and the state represented on the drawing.
  • Follow the named output: Earthing operation condition. Cross-reference its destination and separate the command from confirmation that the equipment responded.
  • Breaker opening alone does not establish isolation.
  • Identify each initiating position, the action being blocked and the consequence of missing feedback. An illustrative logic diagram must not be treated as an operating procedure or proof of a complete safety system.

Information to show or reference

  • Label the source and connection reference for breaker open indication.
  • Identify the destination and defined state of earthing operation condition.
  • Record the equipment or control-document revision supporting this functional block.
  • Check this application limit in the project design: Breaker opening alone does not establish isolation.

A distinction that matters

Breaker opening alone does not establish isolation. This reference describes the named application; it does not establish a new IEC graphical symbol, an ANSI device-function number or an exact manufacturer connection diagram.

Sources you can follow

These public references support the explanation and provide further detail. Their graphics and downloadable files remain with their publishers.

Masterclad medium-voltage switchgear: circuit-breaker section interlocks

Public technical context for switchgear interlocking functions. Breaker control, mechanism, position contacts, racking interlocks and test interfaces. The application text and educational graphic are independently authored; the publisher does not certify this representation.

Schneider Electric · Public reference checked 3 November 2026 · Link only

About this graphic

This illustration was authored independently by Elora Grid to explain the concept. It is not reproduced from a customer drawing, an official standard graphic or a manufacturer CAD file. Its correspondence to an exact IEC or IEEE symbol identifier has not been certified.

SVG and DXF downloads contain this original artwork. Original artwork is available under CC BY 4.0. Third-party references retain their own terms.

Entry JSON · Entry Markdown · Last editorial update: 3 November 2026