Okonite · United States

RHH/RHW-2 · 4/0 AWG 112-09-1411

Okonite-FMR · 600/1000 V · 1-core copper

Illustrative 3D cable outside envelope
3D cable envelope
PlanAASection A–AOutside diameter 0.65 in
2D general arrangement
Supply bus3-phase feeder3 × single-core · 4/0 AWG
Electrical single-line representation

Datasheet

Product code
112-09-1411
Rated voltage
600/1000 V
Conductor
1 × 4/0 AWG Copper
Insulation
EPR
Conductor construction
19 strand(s)
Outside diameter
0.65 in
p. 1p. 2

Using this cable in a drawing

Use the published approximate outside diameter of 0.65 in for the cable outline. The drawing shows a straight, illustrative run of 7.8 in. Supports, terminations and installation clearances are project-specific. p. 2

Published current rating. 260 A · ambient 30 °C · conductor temperature 90 °C · NEC wet column per manufacturer footnote (1); see small-conductor overcurrent limitations. p. 2

Download arrangement DXF · Symbol DXF · Editable 3D envelope

Compare a nearby size

Okonite-FMR · Copper · 600/1000 V. Both columns use the publisher’s original units.

Parameter4/0 AWG · 112-09-14113/0 AWG · 112-09-1391
Overall diameter0.65 in0.6 in
Cable weight730 lb/1000 ft589 lb/1000 ft
Current ratingambient 30 °C · conductor temperature 90 °C · NEC wet column per manufacturer footnote (1); see small-conductor overcurrent limitations260 A225 A
Current ratingambient 30 °C · conductor temperature 75 °C · NEC wet column per manufacturer footnote (1); see small-conductor overcurrent limitations230 A200 A

Calculation parameters and conditions

ParameterValueManufacturer basisSource
Overall diameter0.65 inApproximatep. 2
Cable weight730 lb/1000 ftApproximate net weightp. 2
Operating temperature90 °CWet or dryp. 1
Current rating260 Aambient 30 °C · conductor temperature 90 °C · NEC wet column per manufacturer footnote (1); see small-conductor overcurrent limitationsp. 2
Current rating230 Aambient 30 °C · conductor temperature 75 °C · NEC wet column per manufacturer footnote (1); see small-conductor overcurrent limitationsp. 2

Source and files

Okonite sheet 3-5 · Okonite-FMR Type RHH or RHW-2, VW-1, 600V/1000V Power and Control Cable, Copper Conductor. · H/25070305. Retrieved 2026-11-19.

Open manufacturer PDF · Search this PDF · Download datasheet PDF · Download typed JSON

SHA-256 a421ab23d221ebafce6f1d2d036ebea3ab91847d3fe3c2dc4b25a18247af52c2
Design in 2D and 3D with AI

Design in 2D and 3D with AI

  • Create 2D and 3D from a description
  • Edit in plain words
  • Add equipment from this library
Try it on my own project

Elora Grid · AI design

Design in 2D and 3D with AI

Describe your electrical project. Create a 3D layout and 2D general arrangement.

Design my project

Elora Grid · AI design

Design in 2D and 3D with AI

Describe your electrical project. Create a 3D layout and 2D general arrangement.

“Create an electrical equipment layout with a switchboard, a generator and space for access.”
Design my project

Elora Grid · AI design

Design in 2D and 3D with AI

Describe your electrical project. Create a 3D layout and 2D general arrangement.

Design my project
3D electrical equipment layout