Okonite · United States

XHHW-2 · 350 kcmil 112-31-3541

X-Olene · 600/1000 V · 1-core copper

Illustrative 3D cable outside envelope
3D cable envelope
PlanAASection A–AOutside diameter 0.76 in
2D general arrangement
Supply bus3-phase feeder3 × single-core · 350 kcmil
Electrical single-line representation

Datasheet

Product code
112-31-3541
Rated voltage
600/1000 V
Conductor
1 × 350 kcmil Copper
Insulation
XLPE
Conductor construction
37 strand(s)
Outside diameter
0.76 in
p. 1p. 2

Using this cable in a drawing

Use the published approximate outside diameter of 0.76 in for the cable outline. The drawing shows a straight, illustrative run of 9.12 in. Supports, terminations and installation clearances are project-specific. p. 2

Published current rating. 350 A · ambient 30 °C · conductor temperature 90 °C · NEC wet column per manufacturer footnote (1); see small-conductor overcurrent limitations. p. 2

Download arrangement DXF · Symbol DXF · Editable 3D envelope

Compare a nearby size

X-Olene · Copper · 600/1000 V. Both columns use the publisher’s original units.

Parameter350 kcmil · 112-31-3541250 kcmil · 112-31-3511
Overall diameter0.76 in0.66 in
Cable weight1126 lb/1000 ft814 lb/1000 ft
Current ratingambient 30 °C · conductor temperature 90 °C · NEC wet column per manufacturer footnote (1); see small-conductor overcurrent limitations350 A290 A
Current ratingambient 30 °C · conductor temperature 75 °C · NEC wet column per manufacturer footnote (1); see small-conductor overcurrent limitations310 A255 A

Calculation parameters and conditions

ParameterValueManufacturer basisSource
Overall diameter0.76 inApproximatep. 2
Cable weight1126 lb/1000 ftApproximate net weightp. 2
Operating temperature90 °CWet or dryp. 1
Current rating350 Aambient 30 °C · conductor temperature 90 °C · NEC wet column per manufacturer footnote (1); see small-conductor overcurrent limitationsp. 2
Current rating310 Aambient 30 °C · conductor temperature 75 °C · NEC wet column per manufacturer footnote (1); see small-conductor overcurrent limitationsp. 2

Source and files

Okonite sheet 3-3 · X-Olene Type XHHW-2, 600V/1000V Power and Control Cable, Copper Conductor · H/26020303. Retrieved 2026-11-19.

Open manufacturer PDF · Search this PDF · Download datasheet PDF · Download typed JSON

SHA-256 c3c527be52f0d0e254aa3d495c4db90688e151d9b47894f68b3b6b36c95a041a
Design in 2D and 3D with AI

Design in 2D and 3D with AI

  • Create 2D and 3D from a description
  • Edit in plain words
  • Add equipment from this library
Try it on my own project

Elora Grid · AI design

Design in 2D and 3D with AI

Describe your electrical project. Create a 3D layout and 2D general arrangement.

Design my project

Elora Grid · AI design

Design in 2D and 3D with AI

Describe your electrical project. Create a 3D layout and 2D general arrangement.

“Create an electrical equipment layout with a switchboard, a generator and space for access.”
Design my project

Elora Grid · AI design

Design in 2D and 3D with AI

Describe your electrical project. Create a 3D layout and 2D general arrangement.

Design my project
3D electrical equipment layout