Okonite · United States

RHH/RHW-2 · 2/0 AWG 112-36-3161

X-Olene-FMR · 600/1000 V · 1-core copper

Illustrative 3D cable outside envelope
3D cable envelope
PlanAASection A–AOutside diameter 0.55 in
2D general arrangement
Supply bus3-phase feeder3 × single-core · 2/0 AWG
Electrical single-line representation

Datasheet

Product code
112-36-3161
Rated voltage
600/1000 V
Conductor
1 × 2/0 AWG Copper
Insulation
XLPE
Conductor construction
19 strand(s)
Outside diameter
0.55 in
p. 1p. 2

Using this cable in a drawing

Use the published approximate outside diameter of 0.55 in for the cable outline. The drawing shows a straight, illustrative run of 6.6 in. Supports, terminations and installation clearances are project-specific. p. 2

Published current rating. 195 A · ambient 30 °C · conductor temperature 90 °C · NEC wet column per manufacturer footnote (1); see small-conductor overcurrent limitations. p. 2

Download arrangement DXF · Symbol DXF · Editable 3D envelope

Compare a nearby size

X-Olene-FMR · Copper · 600/1000 V. Both columns use the publisher’s original units.

Parameter2/0 AWG · 112-36-31613/0 AWG · 112-36-3171
Overall diameter0.55 in0.6 in
Cable weight476 lb/1000 ft585 lb/1000 ft
Current ratingambient 30 °C · conductor temperature 90 °C · NEC wet column per manufacturer footnote (1); see small-conductor overcurrent limitations195 A225 A
Current ratingambient 30 °C · conductor temperature 75 °C · NEC wet column per manufacturer footnote (1); see small-conductor overcurrent limitations175 A200 A

Calculation parameters and conditions

ParameterValueManufacturer basisSource
Overall diameter0.55 inApproximatep. 2
Cable weight476 lb/1000 ftApproximate net weightp. 2
Operating temperature90 °CWet or dryp. 1
Current rating195 Aambient 30 °C · conductor temperature 90 °C · NEC wet column per manufacturer footnote (1); see small-conductor overcurrent limitationsp. 2
Current rating175 Aambient 30 °C · conductor temperature 75 °C · NEC wet column per manufacturer footnote (1); see small-conductor overcurrent limitationsp. 2

Source and files

Okonite sheet 3-14 · X-Olene-FMR Type RHH or RHW-2, 600V/1000V Power and Control Cable, Copper Conductor · F/26020314. Retrieved 2026-11-19.

Open manufacturer PDF · Search this PDF · Download datasheet PDF · Download typed JSON

SHA-256 8748a069057b489f14bc758c460c98b058a86c78ecd03eb69df395e9cdd574e8
Design in 2D and 3D with AI

Design in 2D and 3D with AI

  • Create 2D and 3D from a description
  • Edit in plain words
  • Add equipment from this library
Try it on my own project

Elora Grid · AI design

Design in 2D and 3D with AI

Describe your electrical project. Create a 3D layout and 2D general arrangement.

Design my project

Elora Grid · AI design

Design in 2D and 3D with AI

Describe your electrical project. Create a 3D layout and 2D general arrangement.

“Create an electrical equipment layout with a switchboard, a generator and space for access.”
Design my project

Elora Grid · AI design

Design in 2D and 3D with AI

Describe your electrical project. Create a 3D layout and 2D general arrangement.

Design my project
3D electrical equipment layout