RHH/RHW-2 · 300 kcmil 112-36-3201
X-Olene-FMR · 600/1000 V · 1-core copper

Datasheet
- Product code
- 112-36-3201
- Rated voltage
- 600/1000 V
- Conductor
- 1 × 300 kcmil Copper
- Insulation
- XLPE
- Conductor construction
- 37 strand(s)
- Outside diameter
- 0.78 in
Using this cable in a drawing
Use the published approximate outside diameter of 0.78 in for the cable outline. The drawing shows a straight, illustrative run of 9.36 in. Supports, terminations and installation clearances are project-specific. p. 2
Published current rating. 320 A · ambient 30 °C · conductor temperature 90 °C · NEC wet column per manufacturer footnote (1); see small-conductor overcurrent limitations. p. 2
Download arrangement DXF · Symbol DXF · Editable 3D envelope
Compare a nearby size
X-Olene-FMR · Copper · 600/1000 V. Both columns use the publisher’s original units.
| Parameter | 300 kcmil · 112-36-3201 | 350 kcmil · 112-36-3211 |
|---|---|---|
| Overall diameter | 0.78 in | 0.82 in |
| Cable weight | 1035 lb/1000 ft | 1195 lb/1000 ft |
| Current ratingambient 30 °C · conductor temperature 90 °C · NEC wet column per manufacturer footnote (1); see small-conductor overcurrent limitations | 320 A | 350 A |
| Current ratingambient 30 °C · conductor temperature 75 °C · NEC wet column per manufacturer footnote (1); see small-conductor overcurrent limitations | 285 A | 310 A |
Calculation parameters and conditions
| Parameter | Value | Manufacturer basis | Source |
|---|---|---|---|
| Overall diameter | 0.78 in | Approximate | p. 2 |
| Cable weight | 1035 lb/1000 ft | Approximate net weight | p. 2 |
| Operating temperature | 90 °C | Wet or dry | p. 1 |
| Current rating | 320 A | ambient 30 °C · conductor temperature 90 °C · NEC wet column per manufacturer footnote (1); see small-conductor overcurrent limitations | p. 2 |
| Current rating | 285 A | ambient 30 °C · conductor temperature 75 °C · NEC wet column per manufacturer footnote (1); see small-conductor overcurrent limitations | p. 2 |
Source and files
Okonite sheet 3-14 · X-Olene-FMR Type RHH or RHW-2, 600V/1000V Power and Control Cable, Copper Conductor · F/26020314. Retrieved 2026-11-19.
Open manufacturer PDF · Search this PDF · Download datasheet PDF · Download typed JSON
SHA-256 8748a069057b489f14bc758c460c98b058a86c78ecd03eb69df395e9cdd574e8Design in 2D and 3D with AI
- Create 2D and 3D from a description
- Edit in plain words
- Add equipment from this library
Elora Grid · AI design
Design in 2D and 3D with AI
Describe your electrical project. Create a 3D layout and 2D general arrangement.
Elora Grid · AI design
Design in 2D and 3D with AI
Describe your electrical project. Create a 3D layout and 2D general arrangement.
“Create an electrical equipment layout with a switchboard, a generator and space for access.”Design my project
Elora Grid · AI design
Design in 2D and 3D with AI
Describe your electrical project. Create a 3D layout and 2D general arrangement.