Okonite · United States

XHHW-2 · 1000 kcmil 112-36-3501

X-Olene-FMR · 600/1000 V · 1-core copper

Illustrative 3D cable outside envelope
3D cable envelope
PlanAASection A–AOutside diameter 1.22 in
2D general arrangement
Supply bus3-phase feeder3 × single-core · 1000 kcmil
Electrical single-line representation

Datasheet

Product code
112-36-3501
Rated voltage
600/1000 V
Conductor
1 × 1000 kcmil Copper
Insulation
XLPE
Conductor construction
61 strand(s)
Outside diameter
1.22 in
p. 1p. 2

Using this cable in a drawing

Use the published approximate outside diameter of 1.22 in for the cable outline. The drawing shows a straight, illustrative run of 14.64 in. Supports, terminations and installation clearances are project-specific. p. 2

Published current rating. 615 A · ambient 30 °C · conductor temperature 90 °C · NEC wet column per manufacturer footnote (1); see small-conductor overcurrent limitations. p. 2

Download arrangement DXF · Symbol DXF · Editable 3D envelope

Compare a nearby size

X-Olene-FMR · Copper · 600/1000 V. Both columns use the publisher’s original units.

Parameter1000 kcmil · 112-36-3501750 kcmil · 112-36-3491
Overall diameter1.22 in1.07 in
Cable weight3206 lb/1000 ft2426 lb/1000 ft
Current ratingambient 30 °C · conductor temperature 90 °C · NEC wet column per manufacturer footnote (1); see small-conductor overcurrent limitations615 A535 A
Current ratingambient 30 °C · conductor temperature 75 °C · NEC wet column per manufacturer footnote (1); see small-conductor overcurrent limitations545 A475 A

Calculation parameters and conditions

ParameterValueManufacturer basisSource
Overall diameter1.22 inApproximatep. 2
Cable weight3206 lb/1000 ftApproximate net weightp. 2
Operating temperature90 °CWet or dryp. 1
Current rating615 Aambient 30 °C · conductor temperature 90 °C · NEC wet column per manufacturer footnote (1); see small-conductor overcurrent limitationsp. 2
Current rating545 Aambient 30 °C · conductor temperature 75 °C · NEC wet column per manufacturer footnote (1); see small-conductor overcurrent limitationsp. 2

Source and files

Okonite sheet 3-15 · X-Olene-FMR Type XHHW-2, 600V/1000V Power and Control Cable, Copper Conductor · G/26020315. Retrieved 2026-11-19.

Open manufacturer PDF · Search this PDF · Download datasheet PDF · Download typed JSON

SHA-256 f3bb3bbc4ca515882959f2a3e17042e5006cf82b87153177b57e1bf3938fbcbf
Design in 2D and 3D with AI

Design in 2D and 3D with AI

  • Create 2D and 3D from a description
  • Edit in plain words
  • Add equipment from this library
Try it on my own project

Elora Grid · AI design

Design in 2D and 3D with AI

Describe your electrical project. Create a 3D layout and 2D general arrangement.

Design my project

Elora Grid · AI design

Design in 2D and 3D with AI

Describe your electrical project. Create a 3D layout and 2D general arrangement.

“Create an electrical equipment layout with a switchboard, a generator and space for access.”
Design my project

Elora Grid · AI design

Design in 2D and 3D with AI

Describe your electrical project. Create a 3D layout and 2D general arrangement.

Design my project
3D electrical equipment layout