RHH/RHW-2 · 500 kcmil 113-24-2531
Okoguard-Okolon TS-CPE · 2000 V · 1-core copper

Datasheet
- Product code
- 113-24-2531
- Rated voltage
- 2000 V
- Conductor
- 1 × 500 kcmil Copper
- Insulation
- EPR
- Conductor construction
- 37 strand(s)
- Outside diameter
- 1.04 in
Using this cable in a drawing
Use the published approximate outside diameter of 1.04 in for the cable outline. The drawing shows a straight, illustrative run of 12.48 in. Supports, terminations and installation clearances are project-specific. p. 2
Published current rating. 430 A · ambient 30 °C · conductor temperature 90 °C · NEC wet column per manufacturer footnote (1); see small-conductor overcurrent limitations. p. 2
Download arrangement DXF · Symbol DXF · Editable 3D envelope
Compare a nearby size
Okoguard-Okolon TS-CPE · Copper · 2000 V. Both columns use the publisher’s original units.
| Parameter | 500 kcmil · 113-24-2531 | 350 kcmil · 113-24-2471 |
|---|---|---|
| Overall diameter | 1.04 in | 0.92 in |
| Cable weight | 1773 lb/1000 ft | 1286 lb/1000 ft |
| Current ratingambient 30 °C · conductor temperature 90 °C · NEC wet column per manufacturer footnote (1); see small-conductor overcurrent limitations | 430 A | 350 A |
| Current ratingambient 30 °C · conductor temperature 75 °C · NEC wet column per manufacturer footnote (1); see small-conductor overcurrent limitations | 380 A | 310 A |
Calculation parameters and conditions
| Parameter | Value | Manufacturer basis | Source |
|---|---|---|---|
| Overall diameter | 1.04 in | Approximate | p. 2 |
| Cable weight | 1773 lb/1000 ft | Approximate net weight | p. 2 |
| Operating temperature | 90 °C | Wet or dry | p. 1 |
| Current rating | 430 A | ambient 30 °C · conductor temperature 90 °C · NEC wet column per manufacturer footnote (1); see small-conductor overcurrent limitations | p. 2 |
| Current rating | 380 A | ambient 30 °C · conductor temperature 75 °C · NEC wet column per manufacturer footnote (1); see small-conductor overcurrent limitations | p. 2 |
Source and files
Okonite sheet 3-10 · Okoguard-Okolon TS-CPE Type RHH or RHW-2, VW-1, FT-4, CSA RW-90, 2kV Power Cable, Copper Conductor. · L/25070310. Retrieved 2026-11-19.
Open manufacturer PDF · Search this PDF · Download datasheet PDF · Download typed JSON
SHA-256 5d9a1c43d6e954dccd6f0919e937a6dab9dc972f675b5dbef57212e3204855c2Design in 2D and 3D with AI
- Create 2D and 3D from a description
- Edit in plain words
- Add equipment from this library
Elora Grid · AI design
Design in 2D and 3D with AI
Describe your electrical project. Create a 3D layout and 2D general arrangement.
Elora Grid · AI design
Design in 2D and 3D with AI
Describe your electrical project. Create a 3D layout and 2D general arrangement.
“Create an electrical equipment layout with a switchboard, a generator and space for access.”Design my project
Elora Grid · AI design
Design in 2D and 3D with AI
Describe your electrical project. Create a 3D layout and 2D general arrangement.