Okonite · United States

MV-105 · 350 kcmil 115-23-3076

Okoguard-Okoseal · 15 kV · 1-core copper

Illustrative cable cutaway showing the principal materials
3D construction cutaway
PlanAASection A–A6.3 in cable span
2D general arrangement
Supply bus3-phase feeder3 × single-core · 350 kcmil
Electrical single-line representation

Datasheet

Product code
115-23-3076
Rated voltage
15 kV
Conductor
1 × 350 kcmil Copper
Insulation
EPR
Shield / screen
Copper tape
Construction
100% insulation level
Outside diameter
1.26 in
p. 1p. 2

Using this cable in a drawing

Three cables at one outside diameter of clear spacing occupy 6.3 in before tray-side clearances. The published uncovered-tray rating is 610 A. See grounding, spacing and temperature conditions below. p. 2

Published current rating. 440 A · ambient 40 °C · conductor temperature 105 °C · Isolated conduit in air · Three single conductors or triplex. p. 2

Download arrangement DXF · Symbol DXF · Editable 3D envelope

Compare a nearby size

Okoguard-Okoseal · Copper · 15 kV. Both columns use the publisher’s original units.

Parameter350 kcmil · 115-23-3076250 kcmil · 115-23-3074
Overall diameter1.26 in1.17 in
Cable weight1700 lb/1000 ft1330 lb/1000 ft
Current ratingambient 40 °C · conductor temperature 105 °C · Isolated conduit in air · Three single conductors or triplex440 A365 A
Current ratingambient 40 °C · conductor temperature 105 °C · Uncovered cable tray, single-point grounding · Single layer · minimum spacing 1 cable OD610 A495 A

Calculation parameters and conditions

ParameterValueManufacturer basisSource
Overall diameter1.26 inApproximatep. 2
Cable weight1700 lb/1000 ftApproximate net weightp. 2
Operating temperature105 °CContinuousp. 1
Current rating440 Aambient 40 °C · conductor temperature 105 °C · Isolated conduit in air · Three single conductors or triplexp. 2
Current rating610 Aambient 40 °C · conductor temperature 105 °C · Uncovered cable tray, single-point grounding · Single layer · minimum spacing 1 cable ODp. 2

Source and files

Okoguard-Okoseal Type MV-105 · Section 2, Sheet 8 · Z/26040208 · May 2026 PDF. Retrieved 2026-11-19.

Open manufacturer PDF · Search this PDF · Download datasheet PDF · Download typed JSON

SHA-256 81020e97064ac66a93ed861a871da1f3dfe4b4604ae57c7e76dae123e9d2b9d6
Design in 2D and 3D with AI

Design in 2D and 3D with AI

  • Create 2D and 3D from a description
  • Edit in plain words
  • Add equipment from this library
Try it on my own project

Elora Grid · AI design

Design in 2D and 3D with AI

Describe your electrical project. Create a 3D layout and 2D general arrangement.

Design my project

Elora Grid · AI design

Design in 2D and 3D with AI

Describe your electrical project. Create a 3D layout and 2D general arrangement.

“Create an electrical equipment layout with a switchboard, a generator and space for access.”
Design my project

Elora Grid · AI design

Design in 2D and 3D with AI

Describe your electrical project. Create a 3D layout and 2D general arrangement.

Design my project
3D electrical equipment layout