MV-105 · 750 kcmil 115-23-3091
Okoguard-Okoseal · 15 kV · 1-core copper

Datasheet
- Product code
- 115-23-3091
- Rated voltage
- 15 kV
- Conductor
- 1 × 750 kcmil Copper
- Insulation
- EPR
- Shield / screen
- Copper tape
- Jacket / sheath
- PVC
- Standard
- UL 1072, ICEA S-93-639
- Outside diameter
- 1.55 in
Using this cable in a drawing
Three cables at one outside diameter of clear spacing occupy 7.75 in before tray-side clearances. The published uncovered-tray rating is 990 A. See grounding, spacing and temperature conditions below. p. 2
Published current rating. 655 A · Isolated conduit in air · Three single conductors or triplex · conductor temperature 105 °C · ambient 40 °C. p. 2
Download arrangement DXF · Symbol DXF · Editable 3D envelope
Calculation parameters and conditions
| Parameter | Value | Manufacturer basis | Source |
|---|---|---|---|
| Overall diameter | 1.55 in | Approximate | p. 2 |
| Cable weight | 3105 lb/1000 ft | Approximate net weight | p. 2 |
| Current rating | 990 A | Uncovered cable tray, single-point grounding · Single layer · minimum spacing 1 cable OD · conductor temperature 105 °C · ambient 40 °C | p. 2 |
| Current rating | 655 A | Isolated conduit in air · Three single conductors or triplex · conductor temperature 105 °C · ambient 40 °C | p. 2 |
| Operating temperature | 105 °C | Continuous | p. 1 |
| Short-circuit temperature | 250 °C | Short circuit | p. 1 |
Source and files
Okoguard-Okoseal Type MV-105 · Section 2, Sheet 8 · Z/26040208 · May 2026 PDF. Retrieved 2026-11-19.
Open manufacturer PDF · Search this PDF · Download datasheet PDF · Download typed JSON
SHA-256 81020e97064ac66a93ed861a871da1f3dfe4b4604ae57c7e76dae123e9d2b9d6Design in 2D and 3D with AI
- Create 2D and 3D from a description
- Edit in plain words
- Add equipment from this library
Elora Grid · AI design
Design in 2D and 3D with AI
Describe your electrical project. Create a 3D layout and 2D general arrangement.
Elora Grid · AI design
Design in 2D and 3D with AI
Describe your electrical project. Create a 3D layout and 2D general arrangement.
“Create an electrical equipment layout with a switchboard, a generator and space for access.”Design my project
Elora Grid · AI design
Design in 2D and 3D with AI
Describe your electrical project. Create a 3D layout and 2D general arrangement.