Okonite · United States

THHN/THWN-2 · 10 AWG 116-67-1131

Okoseal-N · 600 V · 1-core copper

Illustrative 3D cable outside envelope
3D cable envelope
PlanAASection A–AOutside diameter 0.17 in
2D general arrangement
Supply bus3-phase feeder3 × single-core · 10 AWG
Electrical single-line representation

Datasheet

Product code
116-67-1131
Rated voltage
600 V
Conductor
1 × 10 AWG Copper
Insulation
PVC
Conductor construction
7 strand(s)
Outside diameter
0.17 in
p. 1p. 2

Using this cable in a drawing

Use the published approximate outside diameter of 0.17 in for the cable outline. The drawing shows a straight, illustrative run of 2.04 in. Supports, terminations and installation clearances are project-specific. p. 2

Published current rating. 30 A · ambient 30 °C · conductor temperature 90 °C · NEC wet column per manufacturer footnote (1); see small-conductor overcurrent limitations. p. 2

Download arrangement DXF · Symbol DXF · Editable 3D envelope

Compare a nearby size

Okoseal-N · Copper · 600 V. Both columns use the publisher’s original units.

Parameter10 AWG · 116-67-113112 AWG · 116-67-1101
Overall diameter0.17 in0.13 in
Cable weight40 lb/1000 ft25 lb/1000 ft
Current ratingambient 30 °C · conductor temperature 90 °C · NEC wet column per manufacturer footnote (1); see small-conductor overcurrent limitations30 A20 A
Current ratingambient 30 °C · conductor temperature 75 °C · NEC wet column per manufacturer footnote (1); see small-conductor overcurrent limitations30 A20 A

Calculation parameters and conditions

ParameterValueManufacturer basisSource
Overall diameter0.17 inApproximatep. 2
Cable weight40 lb/1000 ftApproximate net weightp. 2
Operating temperature90 °CWet or dryp. 1
Current rating30 Aambient 30 °C · conductor temperature 90 °C · NEC wet column per manufacturer footnote (1); see small-conductor overcurrent limitationsp. 2
Current rating30 Aambient 30 °C · conductor temperature 75 °C · NEC wet column per manufacturer footnote (1); see small-conductor overcurrent limitationsp. 2

Source and files

Okonite sheet 3-6 · Okoseal-N Type THHN or THWN, VW-1, 600V Power and Control Cable, Copper Conductor. · F/25110306. Retrieved 2026-11-19.

Open manufacturer PDF · Search this PDF · Download datasheet PDF · Download typed JSON

SHA-256 bec21b2a523b971bd7ad903fe9e9fd3d6b9fd0bbed9a876f5cbf30979a842f12
Design in 2D and 3D with AI

Design in 2D and 3D with AI

  • Create 2D and 3D from a description
  • Edit in plain words
  • Add equipment from this library
Try it on my own project

Elora Grid · AI design

Design in 2D and 3D with AI

Describe your electrical project. Create a 3D layout and 2D general arrangement.

Design my project

Elora Grid · AI design

Design in 2D and 3D with AI

Describe your electrical project. Create a 3D layout and 2D general arrangement.

“Create an electrical equipment layout with a switchboard, a generator and space for access.”
Design my project

Elora Grid · AI design

Design in 2D and 3D with AI

Describe your electrical project. Create a 3D layout and 2D general arrangement.

Design my project
3D electrical equipment layout