Okonite · United States

MV-105 · 1/0 AWG 135-23-3301

Okoguard-Okoseal · 15 kV · 1-core aluminum

Illustrative 3D cable outside envelope
3D cable envelope
PlanAASection A–A5.05 in cable span
2D general arrangement
Supply bus3-phase feeder3 × single-core · 1/0 AWG
Electrical single-line representation

Datasheet

Product code
135-23-3301
Rated voltage
15 kV
Conductor
1 × 1/0 AWG Aluminum
Insulation
EPR
Shield / screen
Copper tape
Construction
133% insulation level
Outside diameter
1.01 in
p. 1p. 2

Using this cable in a drawing

Three cables at one outside diameter of clear spacing occupy 5.05 in before tray-side clearances. The published uncovered-tray rating is 225 A. See grounding, spacing and temperature conditions below. p. 2

Published current rating. 170 A · ambient 40 °C · conductor temperature 105 °C · Isolated conduit in air · Three single conductors or triplex. p. 2

Download arrangement DXF · Symbol DXF · Editable 3D envelope

Compare a nearby size

Okoguard-Okoseal · Aluminum · 15 kV. Both columns use the publisher’s original units.

Parameter1/0 AWG · 135-23-33012/0 AWG · 135-23-3302
Overall diameter1.01 in1.14 in
Cable weight656 lb/1000 ft715 lb/1000 ft
Current ratingambient 40 °C · conductor temperature 105 °C · Isolated conduit in air · Three single conductors or triplex170 A200 A
Current ratingambient 40 °C · conductor temperature 105 °C · Uncovered cable tray, single-point grounding · Single layer · minimum spacing 1 cable OD225 A260 A

Calculation parameters and conditions

ParameterValueManufacturer basisSource
Overall diameter1.01 inApproximatep. 2
Cable weight656 lb/1000 ftApproximate net weightp. 2
Operating temperature105 °CContinuousp. 1
Current rating170 Aambient 40 °C · conductor temperature 105 °C · Isolated conduit in air · Three single conductors or triplexp. 2
Current rating225 Aambient 40 °C · conductor temperature 105 °C · Uncovered cable tray, single-point grounding · Single layer · minimum spacing 1 cable ODp. 2

Source and files

Okonite sheet 2-59 · 1/C, 15 kV Okoguard Okoseal, Copper Tape Shielded, Aluminum Conductor, 15 kV 100% and 133% Insulation Level, 105°C Rating, Type MV-105 · K/26040259. Retrieved 2026-11-19.

Open manufacturer PDF · Search this PDF · Download datasheet PDF · Download typed JSON

SHA-256 04ce90883ae34c435167c480cd8f4ed90a10db21a58c8c8dc4cb2286ad8d0941
Design in 2D and 3D with AI

Design in 2D and 3D with AI

  • Create 2D and 3D from a description
  • Edit in plain words
  • Add equipment from this library
Try it on my own project

Elora Grid · AI design

Design in 2D and 3D with AI

Describe your electrical project. Create a 3D layout and 2D general arrangement.

Design my project

Elora Grid · AI design

Design in 2D and 3D with AI

Describe your electrical project. Create a 3D layout and 2D general arrangement.

“Create an electrical equipment layout with a switchboard, a generator and space for access.”
Design my project

Elora Grid · AI design

Design in 2D and 3D with AI

Describe your electrical project. Create a 3D layout and 2D general arrangement.

Design my project
3D electrical equipment layout