Functional block · EBI

Earthing-switch-open breaker interlock

Functional block · Switchgear

An independently authored application reference. The drawing shows the named function or circuit relationship; use the project legend and selected equipment documentation for its drafting form and connections.

Browse this installation focus

In plain English

What this block does

Blocks closing toward a circuit when the associated earthing switch is not proved open.

A simple example

In a switchgear feeder panel, a control diagram can prevent an incompatible combination of breaker, disconnector and earthing-switch positions. The physical equipment documents determine which restrictions are mechanically enforced. For this reference, the drawing identifies “Earthing-switch position” at the input and “Breaker closing inhibit” at the output. All relevant earthing points must be considered.

Earthing-switch positionEBIBreaker closing inhibit
A reading guide. The entry's original illustration and input/output facts describe this application.

What the drawings help you do

Start at the named input: Earthing-switch position. Identify its source device or document and the state represented on the drawing. Follow the named output: Breaker closing inhibit. Cross-reference its destination and separate the command from confirmation that the equipment responded.

Input
Earthing-switch position
Output
Breaker closing inhibit
Application reference
An explanation of a named drawing function or circuit relationship; the project documents define the equipment and its connections.

Read the source: Masterclad medium-voltage switchgear: circuit-breaker section interlocks

Schematic · EBIEarthing-switch-open breaker interlock: original educational illustration
Original educational illustrationSee source and graphic notes

What it represents

Blocks closing toward a circuit when the associated earthing switch is not proved open. An interlocking function permits or blocks an operation according to the positions and conditions of related equipment. Electrical, mechanical and trapped-key interlocks implement different parts of a coordinated operating philosophy.

In a switchgear feeder panel, a control diagram can prevent an incompatible combination of breaker, disconnector and earthing-switch positions. The physical equipment documents determine which restrictions are mechanically enforced. For this reference, the drawing identifies “Earthing-switch position” at the input and “Breaker closing inhibit” at the output. All relevant earthing points must be considered.

Identify each initiating position, the action being blocked and the consequence of missing feedback. An illustrative logic diagram must not be treated as an operating procedure or proof of a complete safety system. The functional block is an independent explanation of this named application. Equipment-specific ratings, terminal connections and operating conditions must be established in the project documentation.

How to read it

  • Start at the named input: Earthing-switch position. Identify its source device or document and the state represented on the drawing.
  • Follow the named output: Breaker closing inhibit. Cross-reference its destination and separate the command from confirmation that the equipment responded.
  • All relevant earthing points must be considered.
  • Identify each initiating position, the action being blocked and the consequence of missing feedback. An illustrative logic diagram must not be treated as an operating procedure or proof of a complete safety system.

Information to show or reference

  • Label the source and connection reference for earthing-switch position.
  • Identify the destination and defined state of breaker closing inhibit.
  • Record the equipment or control-document revision supporting this functional block.
  • Check this application limit in the project design: All relevant earthing points must be considered.

A distinction that matters

All relevant earthing points must be considered. This reference describes the named application; it does not establish a new IEC graphical symbol, an ANSI device-function number or an exact manufacturer connection diagram.

Sources you can follow

These public references support the explanation and provide further detail. Their graphics and downloadable files remain with their publishers.

Masterclad medium-voltage switchgear: circuit-breaker section interlocks

Public technical context for switchgear interlocking functions. Breaker control, mechanism, position contacts, racking interlocks and test interfaces. The application text and educational graphic are independently authored; the publisher does not certify this representation.

Schneider Electric · Public reference checked 3 November 2026 · Link only

About this graphic

This illustration was authored independently by Elora Grid to explain the concept. It is not reproduced from a customer drawing, an official standard graphic or a manufacturer CAD file. Its correspondence to an exact IEC or IEEE symbol identifier has not been certified.

SVG and DXF downloads contain this original artwork. Original artwork is available under CC BY 4.0. Third-party references retain their own terms.

Entry JSON · Entry Markdown · Last editorial update: 3 November 2026