3CALX11HD · 240 mm²
Medium Voltage · 6.35/11 kV · 3-core aluminium

Datasheet
- Product code
- 3CALX11HD
- Rated voltage
- 6.35/11 kV
- Conductor
- 3 × 240 mm² Aluminium
- Insulation
- XLPE
- Shield / screen
- Copper wire
- Armour
- Unarmoured
- Jacket / sheath
- 5V-90 PVC
- Standard
- AS/NZS 1429.1
- Outside diameter
- 70.3 mm
Using this cable in a drawing
Use the published approximate outside diameter of 70.3 mm for the cable outline. The drawing shows a straight, illustrative run of 843.6 mm. Supports, terminations and installation clearances are project-specific. p. 77
Published current rating. 370 A · Direct buried, compacted backfill · soil temperature 25 °C · soil thermal resistivity 1.2 °C·m/W · depth 0.8 m · Single three-core cable, balanced load, screens bonded at both ends · conductor temperature 90 °C. p. 77p. 131
Download arrangement DXF · Symbol DXF · Editable 3D envelope
Compare a nearby size
Medium Voltage · Aluminium · 6.35/11 kV. Both columns use the publisher’s original units.
| Parameter | 240 mm² · 3CALX11HD | 185 mm² · 3CALX11HD |
|---|---|---|
| DC resistance | 0.125 Ω/km | 0.164 Ω/km |
| Current ratingDirect buried, compacted backfill · soil temperature 25 °C · soil thermal resistivity 1.2 °C·m/W · depth 0.8 m · Single three-core cable, balanced load, screens bonded at both ends · conductor temperature 90 °C | 370 A | 325 A |
| Current ratingSingleway duct, one cable per duct · soil temperature 25 °C · soil thermal resistivity 1.2 °C·m/W · depth 0.8 m · Single three-core cable, balanced load, screens bonded at both ends · conductor temperature 90 °C | 320 A | 275 A |
| Current ratingFree air, shaded from direct sun · minimum wall clearance 0.5 cable OD · ambient 40 °C · Single three-core cable, balanced load, screens bonded at both ends · conductor temperature 90 °C | 405 A | 345 A |
| Overall diameter | 70.3 mm | 65.3 mm |
| Cable weight | 500 kg/100 m | 425 kg/100 m |
Worked three-phase voltage drop
Adjust the one-way run length and load. This balanced-load estimate uses √3 × I × L × (R cos φ + X sin φ), with L in km, 0.162 Ω/km AC resistance at 90°C and 0.0912 Ω/km reactance at 50 Hz. Charging current is omitted. p. 77
Calculation parameters and conditions
| Parameter | Value | Manufacturer basis | Source |
|---|---|---|---|
| DC resistance | 0.125 Ω/km | Maximum · conductor temperature 20 °C | p. 77 |
| AC resistance | 0.162 Ω/km | conductor temperature 90 °C · frequency 50 Hz · Three-core cable | p. 77 |
| Capacitance | 0.462 µF/km | Phase to earth | p. 77 |
| Inductive reactance | 0.0912 Ω/km | frequency 50 Hz · Three-core cable · Unspecified | p. 77 |
| Current rating | 370 A | Direct buried, compacted backfill · soil temperature 25 °C · soil thermal resistivity 1.2 °C·m/W · depth 0.8 m · Single three-core cable, balanced load, screens bonded at both ends · conductor temperature 90 °C | p. 77p. 131 |
| Current rating | 320 A | Singleway duct, one cable per duct · soil temperature 25 °C · soil thermal resistivity 1.2 °C·m/W · depth 0.8 m · Single three-core cable, balanced load, screens bonded at both ends · conductor temperature 90 °C | p. 77p. 131 |
| Current rating | 405 A | Free air, shaded from direct sun · minimum wall clearance 0.5 cable OD · ambient 40 °C · Single three-core cable, balanced load, screens bonded at both ends · conductor temperature 90 °C | p. 77p. 131 |
| Overall diameter | 70.3 mm | Approximate | p. 77 |
| Cable weight | 500 kg/100 m | Approximate mass | p. 77 |
| Minimum bend radius | 1270 mm | During installation, PVC | p. 77 |
| Operating temperature | 90 °C | Maximum continuous | p. 76 |
| Short-circuit temperature | 250 °C | maximum duration 5 s | p. 131 |
Source and files
Prysmian Medium Voltage Cables · 3CALX11HD · April 2015. Retrieved 2026-11-19.
Open manufacturer PDF · Search this PDF · Download datasheet PDF · Download typed JSON
SHA-256 4737d3bec581feeca321663725acccf526e1d307e2256e8038ebd1e0765a1a40Design in 2D and 3D with AI
- Create 2D and 3D from a description
- Edit in plain words
- Add equipment from this library
Elora Grid · AI design
Design in 2D and 3D with AI
Describe your electrical project. Create a 3D layout and 2D general arrangement.
Elora Grid · AI design
Design in 2D and 3D with AI
Describe your electrical project. Create a 3D layout and 2D general arrangement.
“Create an electrical equipment layout with a switchboard, a generator and space for access.”Design my project
Elora Grid · AI design
Design in 2D and 3D with AI
Describe your electrical project. Create a 3D layout and 2D general arrangement.