Prysmian · Australia

3CALX22LD · 95 mm²

Medium Voltage · 12.7/22 kV · 3-core aluminium

Illustrative 3D cable outside envelope
3D cable envelope
PlanAASection A–AOutside diameter 64.7 mm
2D general arrangement
Supply bus3-phase feeder1 × 3-core · 95 mm²
Electrical single-line representation

Datasheet

Product code
3CALX22LD
Rated voltage
12.7/22 kV
Conductor
3 × 95 mm² Aluminium
Insulation
XLPE
Armour
Unarmoured
Construction
light duty screened unarmoured
Outside diameter
64.7 mm
p. 96p. 97

Using this cable in a drawing

Use the published approximate outside diameter of 64.7 mm for the cable outline. The drawing shows a straight, illustrative run of 776.4 mm. Supports, terminations and installation clearances are project-specific. p. 97

Published current rating. 235 A · Direct buried, compacted backfill · soil temperature 25 °C · soil thermal resistivity 1.2 °C·m/W · depth 0.8 m · Single three-core cable, balanced load, screens bonded at both ends · conductor temperature 90 °C. p. 97p. 131

Download arrangement DXF · Symbol DXF · Editable 3D envelope

Compare a nearby size

Medium Voltage · Aluminium · 12.7/22 kV. Both columns use the publisher’s original units.

Parameter95 mm² · 3CALX22LD120 mm² · 3CALX22LD
Overall diameter64.7 mm67.8 mm
Cable weight340 kg/100 m380 kg/100 m
DC resistance0.32 Ω/km0.253 Ω/km
Current ratingDirect buried, compacted backfill · soil temperature 25 °C · soil thermal resistivity 1.2 °C·m/W · depth 0.8 m · Single three-core cable, balanced load, screens bonded at both ends · conductor temperature 90 °C235 A255 A
Current ratingSingleway duct, one cable per duct · soil temperature 25 °C · soil thermal resistivity 1.2 °C·m/W · depth 0.8 m · Single three-core cable, balanced load, screens bonded at both ends · conductor temperature 90 °C190 A220 A

Worked three-phase voltage drop

Adjust the one-way run length and load. This balanced-load estimate uses √3 × I × L × (R cos φ + X sin φ), with L in km, 0.411 Ω/km AC resistance at 90°C and 0.115 Ω/km reactance at 50 Hz. Charging current is omitted. p. 97

14.55 V · 0.066%

Calculation parameters and conditions

ParameterValueManufacturer basisSource
Overall diameter64.7 mmApproximatep. 97
Cable weight340 kg/100 mApproximate massp. 97
DC resistance0.32 Ω/kmMaximum · conductor temperature 20 °Cp. 97
Minimum bend radius1170 mmDuring installation, PVCp. 97
AC resistance0.411 Ω/kmconductor temperature 90 °C · frequency 50 Hz · Three-core cablep. 97
Inductive reactance0.115 Ω/kmfrequency 50 Hz · Three-core cable · Unspecifiedp. 97
Current rating235 ADirect buried, compacted backfill · soil temperature 25 °C · soil thermal resistivity 1.2 °C·m/W · depth 0.8 m · Single three-core cable, balanced load, screens bonded at both ends · conductor temperature 90 °Cp. 97p. 131
Current rating190 ASingleway duct, one cable per duct · soil temperature 25 °C · soil thermal resistivity 1.2 °C·m/W · depth 0.8 m · Single three-core cable, balanced load, screens bonded at both ends · conductor temperature 90 °Cp. 97p. 131

Source and files

Prysmian Medium Voltage Cables · 3CALX11HD · April 2015. Retrieved 2026-11-19.

Open manufacturer PDF · Search this PDF · Download datasheet PDF · Download typed JSON

SHA-256 4737d3bec581feeca321663725acccf526e1d307e2256e8038ebd1e0765a1a40
Design in 2D and 3D with AI

Design in 2D and 3D with AI

  • Create 2D and 3D from a description
  • Edit in plain words
  • Add equipment from this library
Try it on my own project

Elora Grid · AI design

Design in 2D and 3D with AI

Describe your electrical project. Create a 3D layout and 2D general arrangement.

Design my project

Elora Grid · AI design

Design in 2D and 3D with AI

Describe your electrical project. Create a 3D layout and 2D general arrangement.

“Create an electrical equipment layout with a switchboard, a generator and space for access.”
Design my project

Elora Grid · AI design

Design in 2D and 3D with AI

Describe your electrical project. Create a 3D layout and 2D general arrangement.

Design my project
3D electrical equipment layout