3CALX3LD · 50 mm²
Medium Voltage · 1.9/3.3 kV · 3-core aluminium

Datasheet
- Product code
- 3CALX3LD
- Rated voltage
- 1.9/3.3 kV
- Conductor
- 3 × 50 mm² Aluminium
- Insulation
- XLPE
- Armour
- Unarmoured
- Construction
- light duty screened unarmoured
- Outside diameter
- 40.7 mm
Using this cable in a drawing
Use the published approximate outside diameter of 40.7 mm for the cable outline. The drawing shows a straight, illustrative run of 488.4 mm. Supports, terminations and installation clearances are project-specific. p. 25
Published current rating. 150 A · Direct buried, compacted backfill · soil temperature 25 °C · soil thermal resistivity 1.2 °C·m/W · depth 0.8 m · Single three-core cable, balanced load, screens bonded at both ends · conductor temperature 90 °C. p. 25p. 131
Download arrangement DXF · Symbol DXF · Editable 3D envelope
Compare a nearby size
Medium Voltage · Aluminium · 1.9/3.3 kV. Both columns use the publisher’s original units.
| Parameter | 50 mm² · 3CALX3LD | 35 mm² · 3CALX3LD |
|---|---|---|
| Overall diameter | 40.7 mm | 38.4 mm |
| Cable weight | 150 kg/100 m | 130 kg/100 m |
| DC resistance | 0.641 Ω/km | 0.868 Ω/km |
| Current ratingDirect buried, compacted backfill · soil temperature 25 °C · soil thermal resistivity 1.2 °C·m/W · depth 0.8 m · Single three-core cable, balanced load, screens bonded at both ends · conductor temperature 90 °C | 150 A | 125 A |
| Current ratingSingleway duct, one cable per duct · soil temperature 25 °C · soil thermal resistivity 1.2 °C·m/W · depth 0.8 m · Single three-core cable, balanced load, screens bonded at both ends · conductor temperature 90 °C | 130 A | 110 A |
Worked three-phase voltage drop
Adjust the one-way run length and load. This balanced-load estimate uses √3 × I × L × (R cos φ + X sin φ), with L in km, 0.822 Ω/km AC resistance at 90°C and 0.11 Ω/km reactance at 50 Hz. Charging current is omitted. p. 25
Calculation parameters and conditions
| Parameter | Value | Manufacturer basis | Source |
|---|---|---|---|
| Overall diameter | 40.7 mm | Approximate | p. 25 |
| Cable weight | 150 kg/100 m | Approximate mass | p. 25 |
| DC resistance | 0.641 Ω/km | Maximum · conductor temperature 20 °C | p. 25 |
| Minimum bend radius | 730 mm | During installation, PVC | p. 25 |
| AC resistance | 0.822 Ω/km | conductor temperature 90 °C · frequency 50 Hz · Three-core cable | p. 25 |
| Inductive reactance | 0.11 Ω/km | frequency 50 Hz · Three-core cable · Unspecified | p. 25 |
| Current rating | 150 A | Direct buried, compacted backfill · soil temperature 25 °C · soil thermal resistivity 1.2 °C·m/W · depth 0.8 m · Single three-core cable, balanced load, screens bonded at both ends · conductor temperature 90 °C | p. 25p. 131 |
| Current rating | 130 A | Singleway duct, one cable per duct · soil temperature 25 °C · soil thermal resistivity 1.2 °C·m/W · depth 0.8 m · Single three-core cable, balanced load, screens bonded at both ends · conductor temperature 90 °C | p. 25p. 131 |
Source and files
Prysmian Medium Voltage Cables · 3CALX11HD · April 2015. Retrieved 2026-11-19.
Open manufacturer PDF · Search this PDF · Download datasheet PDF · Download typed JSON
SHA-256 4737d3bec581feeca321663725acccf526e1d307e2256e8038ebd1e0765a1a40Design in 2D and 3D with AI
- Create 2D and 3D from a description
- Edit in plain words
- Add equipment from this library
Elora Grid · AI design
Design in 2D and 3D with AI
Describe your electrical project. Create a 3D layout and 2D general arrangement.
Elora Grid · AI design
Design in 2D and 3D with AI
Describe your electrical project. Create a 3D layout and 2D general arrangement.
“Create an electrical equipment layout with a switchboard, a generator and space for access.”Design my project
Elora Grid · AI design
Design in 2D and 3D with AI
Describe your electrical project. Create a 3D layout and 2D general arrangement.
