Prysmian · Australia

3CCUX33HD · 240 mm²

Medium Voltage · 19/33 kV · 3-core copper

Illustrative 3D cable outside envelope
3D cable envelope
PlanAASection A–AOutside diameter 91.8 mm
2D general arrangement
Supply bus3-phase feeder1 × 3-core · 240 mm²
Electrical single-line representation

Datasheet

Product code
3CCUX33HD
Rated voltage
19/33 kV
Conductor
3 × 240 mm² Copper
Insulation
XLPE
Armour
Unarmoured
Construction
heavy duty screened unarmoured
Outside diameter
91.8 mm
p. 112p. 113

Using this cable in a drawing

Use the published approximate outside diameter of 91.8 mm for the cable outline. The drawing shows a straight, illustrative run of 1101.6 mm. Supports, terminations and installation clearances are project-specific. p. 113

Published current rating. 486 A · Direct buried, compacted backfill · soil temperature 25 °C · soil thermal resistivity 1.2 °C·m/W · depth 0.8 m · Single three-core cable, balanced load, screens bonded at both ends · conductor temperature 90 °C. p. 113p. 131

Download arrangement DXF · Symbol DXF · Editable 3D envelope

Compare a nearby size

Medium Voltage · Copper · 19/33 kV. Both columns use the publisher’s original units.

Parameter240 mm² · 3CCUX33HD185 mm² · 3CCUX33HD
Overall diameter91.8 mm86.7 mm
Cable weight1160 kg/100 m970 kg/100 m
DC resistance0.0754 Ω/km0.0991 Ω/km
Current ratingDirect buried, compacted backfill · soil temperature 25 °C · soil thermal resistivity 1.2 °C·m/W · depth 0.8 m · Single three-core cable, balanced load, screens bonded at both ends · conductor temperature 90 °C486 A410 A
Current ratingSingleway duct, one cable per duct · soil temperature 25 °C · soil thermal resistivity 1.2 °C·m/W · depth 0.8 m · Single three-core cable, balanced load, screens bonded at both ends · conductor temperature 90 °C402 A360 A

Worked three-phase voltage drop

Adjust the one-way run length and load. This balanced-load estimate uses √3 × I × L × (R cos φ + X sin φ), with L in km, 0.0978 Ω/km AC resistance at 90°C and 0.108 Ω/km reactance at 50 Hz. Charging current is omitted. p. 113

4.68 V · 0.014%

Calculation parameters and conditions

ParameterValueManufacturer basisSource
Overall diameter91.8 mmApproximatep. 113
Cable weight1160 kg/100 mApproximate massp. 113
DC resistance0.0754 Ω/kmMaximum · conductor temperature 20 °Cp. 113
Minimum bend radius1650 mmDuring installation, PVCp. 113
AC resistance0.0978 Ω/kmconductor temperature 90 °C · frequency 50 Hz · Three-core cablep. 113
Inductive reactance0.108 Ω/kmfrequency 50 Hz · Three-core cable · Unspecifiedp. 113
Current rating486 ADirect buried, compacted backfill · soil temperature 25 °C · soil thermal resistivity 1.2 °C·m/W · depth 0.8 m · Single three-core cable, balanced load, screens bonded at both ends · conductor temperature 90 °Cp. 113p. 131
Current rating402 ASingleway duct, one cable per duct · soil temperature 25 °C · soil thermal resistivity 1.2 °C·m/W · depth 0.8 m · Single three-core cable, balanced load, screens bonded at both ends · conductor temperature 90 °Cp. 113p. 131

Source and files

Prysmian Medium Voltage Cables · 3CALX11HD · April 2015. Retrieved 2026-11-19.

Open manufacturer PDF · Search this PDF · Download datasheet PDF · Download typed JSON

SHA-256 4737d3bec581feeca321663725acccf526e1d307e2256e8038ebd1e0765a1a40
Design in 2D and 3D with AI

Design in 2D and 3D with AI

  • Create 2D and 3D from a description
  • Edit in plain words
  • Add equipment from this library
Try it on my own project

Elora Grid · AI design

Design in 2D and 3D with AI

Describe your electrical project. Create a 3D layout and 2D general arrangement.

Design my project

Elora Grid · AI design

Design in 2D and 3D with AI

Describe your electrical project. Create a 3D layout and 2D general arrangement.

“Create an electrical equipment layout with a switchboard, a generator and space for access.”
Design my project

Elora Grid · AI design

Design in 2D and 3D with AI

Describe your electrical project. Create a 3D layout and 2D general arrangement.

Design my project
3D electrical equipment layout