Prysmian · Australia

3CCUX3LDA · 150 mm²

Medium Voltage · 1.9/3.3 kV · 3-core copper

Illustrative 3D cable outside envelope
3D cable envelope
PlanAASection A–AOutside diameter 64.2 mm
2D general arrangement
Supply bus3-phase feeder1 × 3-core · 150 mm²
Electrical single-line representation

Datasheet

Product code
3CCUX3LDA
Rated voltage
1.9/3.3 kV
Conductor
3 × 150 mm² Copper
Insulation
XLPE
Armour
Armoured
Construction
light duty screened armoured
Outside diameter
64.2 mm
p. 14p. 15

Using this cable in a drawing

Use the published approximate outside diameter of 64.2 mm for the cable outline. The drawing shows a straight, illustrative run of 770.4 mm. Supports, terminations and installation clearances are project-specific. p. 15

Published current rating. 365 A · Direct buried, compacted backfill · soil temperature 25 °C · soil thermal resistivity 1.2 °C·m/W · depth 0.8 m · Single three-core cable, balanced load, screens bonded at both ends · conductor temperature 90 °C. p. 15p. 131

Download arrangement DXF · Symbol DXF · Editable 3D envelope

Compare a nearby size

Medium Voltage · Copper · 1.9/3.3 kV. Both columns use the publisher’s original units.

Parameter150 mm² · 3CCUX3LDA120 mm² · 3CCUX3LDA
Overall diameter64.2 mm61 mm
Cable weight870 kg/100 m765 kg/100 m
DC resistance0.124 Ω/km0.153 Ω/km
Current ratingDirect buried, compacted backfill · soil temperature 25 °C · soil thermal resistivity 1.2 °C·m/W · depth 0.8 m · Single three-core cable, balanced load, screens bonded at both ends · conductor temperature 90 °C365 A330 A
Current ratingSingleway duct, one cable per duct · soil temperature 25 °C · soil thermal resistivity 1.2 °C·m/W · depth 0.8 m · Single three-core cable, balanced load, screens bonded at both ends · conductor temperature 90 °C310 A275 A

Calculation parameters and conditions

ParameterValueManufacturer basisSource
Overall diameter64.2 mmApproximatep. 15
Cable weight870 kg/100 mApproximate massp. 15
DC resistance0.124 Ω/kmMaximum · conductor temperature 20 °Cp. 15
Minimum bend radius1160 mmDuring installation, PVCp. 15
AC resistance0.16 Ω/kmconductor temperature 90 °C · frequency 50 Hz · Three-core cablep. 15
Current rating365 ADirect buried, compacted backfill · soil temperature 25 °C · soil thermal resistivity 1.2 °C·m/W · depth 0.8 m · Single three-core cable, balanced load, screens bonded at both ends · conductor temperature 90 °Cp. 15p. 131
Current rating310 ASingleway duct, one cable per duct · soil temperature 25 °C · soil thermal resistivity 1.2 °C·m/W · depth 0.8 m · Single three-core cable, balanced load, screens bonded at both ends · conductor temperature 90 °Cp. 15p. 131

Source and files

Prysmian Medium Voltage Cables · 3CALX11HD · April 2015. Retrieved 2026-11-19.

Open manufacturer PDF · Search this PDF · Download datasheet PDF · Download typed JSON

SHA-256 4737d3bec581feeca321663725acccf526e1d307e2256e8038ebd1e0765a1a40
Design in 2D and 3D with AI

Design in 2D and 3D with AI

  • Create 2D and 3D from a description
  • Edit in plain words
  • Add equipment from this library
Try it on my own project

Elora Grid · AI design

Design in 2D and 3D with AI

Describe your electrical project. Create a 3D layout and 2D general arrangement.

Design my project

Elora Grid · AI design

Design in 2D and 3D with AI

Describe your electrical project. Create a 3D layout and 2D general arrangement.

“Create an electrical equipment layout with a switchboard, a generator and space for access.”
Design my project

Elora Grid · AI design

Design in 2D and 3D with AI

Describe your electrical project. Create a 3D layout and 2D general arrangement.

Design my project
3D electrical equipment layout